SpChAlmTime: Time delay for spring charging time alarm.tDGasPresAlm: Time delay for gas pressure alarm.tDGasPresLO: Time delay for gas pressure lockout.DirCoef: Directional coefficient for circuit breaker life calculation.RatedOperCurr: Rated operating current of the circuit breaker.RatedFltCurr: Rated fault current of the circuit breaker.OperNoRated: Number of operations possible at rated current.OperNoFault: Number of operations possible at rated fault current.CBLifeAlmLevel: Alarm level for circuit breaker remaining life.AccSelCal: Selection between the method of calculation of accumulated energy.OperTimeDelay: Time delay between change of status of trip output and start of maincontact separation.17.5 Event function EVENT IP14590-1 v217.5.1 IdentificationSEMOD167950-2 v2Function description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberEvent function EVENTS00946 V1 EN-US-17.5.2 Application M12805-6 v11When using a Substation Automation system with LON or SPA communication, time-tagged events can be sent at change or cyclically from the IED to the station level.These events are created from any available signal in the IED that is connected to theEvent function (EVENT). The EVENT function block is used for remotecommunication.Analog, integer and double indication values are also transferred through the EVENTfunction.Section 17 1MRK 511 401-UUS AMonitoring530 Bay control REC670 2.2 ANSIApplication manual