One press changes the enumerated value by one step in the parameter specificorder.4.1.12 Committing settingsEditable values are stored either in RAM or in non-volatile flash memory. Valuesstored in flash memory are in effect also after reboot.Some parameters have an edit-copy. If editing is cancelled, the values with an edit-copy are immediately restored to the original value. The values without an edit-copy,such as string values, are restored to the original value only after a reboot even thoughthe edited value is not stored in the flash memory.1. Press to confirm any changes.2. Press to move upwards in the menu tree or to enter the Main Menu.3. To save the changes in non-volatile memory, select Yes and press .A070891 V3 ENFigure 19: Confirming settings• To exit without saving changes, select No and press .• If the parameter has an edit-copy, the original parameter value isrestored.• If the parameter does not have an edit-copy, the edited parametervalue remains visible until you reboot the IED. However, the editedvalue is not stored in non-volatile memory and the reboot restoresthe original value.• To cancel saving settings, select Cancel and press . The value returnsto editing mode.After certain parameters are changed, the IED has to be restarted.1MRS756708 A Section 4Using HMI locally or via web interface615 series 39Operation Manual