A071222 V2 ENFigure 61: WarningTable 17:Warning indications and codesWarning indication Warning code Additional informationWarningWatchdog reset10 A watchdog reset has occurred.WarningPower down det.11 The auxiliary supply voltage has droppedtoo low.WarningIEC61850 error20 Error when building the IEC 61850 datamodel.WarningModbus error21 Error in the Modbus communication.WarningDNP3 error22 Error in the DNP3 communication.WarningDataset error24 Error in the Data set(s).WarningReport cont. error25 Error in the Report control block(s).WarningGOOSE contr. error26 Error in the GOOSE control block(s).WarningSCL config error27 Error in the SCL configuration file or the fileis missing.WarningLogic error28 Too many connections in theconfiguration.WarningSMT logic error29 Error in the SMT connections.WarningGOOSE input error30 Error in the GOOSE connections.WarningGOOSE rec. error32 Error in the GOOSE message receiving.WarningAFL error33 Analog channel configuration error.WarningUnack card comp.40 A new composition has not beenacknowledged/accepted.Table continues on next page1MRS756708 A Section 7Troubleshooting615 series 85Operation Manual