The time between selecting the object and giving a control commandis restricted by an adjustable time-out. When an object is selected, thecontrol command has to be given within this time.6.3 Resetting IED6.3.1 Clearing and acknowledging via LHMIYou can reset, acknowledge or clear all messages and indications, including LEDsand latched outputs as well as registers and recordings, with the Clear button. Pressingthe Clear button activates a selection menu, where you can choose which clearanceor reset function you want to make. You can also clear events and alarms assigned toalarm LEDs with the Clear button.1. Press to activate the Clear view.All the items that can be cleared are shown:• Indications and LEDs• Alarm LEDs• Recorded data• Events• Disturbance records• Temperature functions• Trip lockout functionsA070860 V2 ENFigure 52: Clear view2. Select the item to be cleared with or .3. Press , change the value with or and press again.The item is now cleared.4. Repeat the steps to clear other items.Section 6 1MRS756708 AOperating procedures74 615 seriesOperation Manual