BitA RegA IEC 61850 name SA name Description Values Alternative 3 0/1=Off/On3548 221.12 .SPCSO7.stVal Output 7 0/1=Off/On3549 221.13 .mcd Alternative 2 0/1=Off/On Alternative 3 0/1=Off/On3550 221.14 .SPCSO8.stVal Output 8 0/1=Off/On3551 221.15 .mcd Alternative 2 0/1=Off/On Alternative 3 0/1=Off/On2.3.1.22 LD0.PHIPTOC1 Three-phase non-directional overcurrent protection,instantaneous stage (1)Table 25:LD0.PHIPTOC1 Three-phase non-directional overcurrent protection, instantaneous stage (1)BitA RegA IEC 61850 name SA name Description ValuesLD0.PHIPTOC12890 180.10 .Str.general START General start 1=Start2891 180.11 .mcd2892 180.12 .Str.phsA phsA start 1=Start2893 180.13 .mcd2894 180.14 .Str.phsB phsB start 1=Start2895 180.15 .mcd2896 181.00 .Str.phsC phsC start 1=Start2897 181.01 .mcd2898 181.02 .Op.general OPERATE General operate 1=Operate2899 181.03 .mcd2.3.1.23 LD0.PHLPTOC1 Three-phase non-directional overcurrent protection,low stage (1)Table 26:LD0.PHLPTOC1 Three-phase non-directional overcurrent protection, low stage (1)BitA RegA IEC 61850 name SA name Description ValuesLD0.PHLPTOC12880 180.00 .Str.general START General start 1=Start2881 180.01 .mcd2882 180.02 .Str.phsA Phs A start 1=Start2883 180.03 .mcd2884 180.04 .Str.phsB Phs B start 1=Start2885 180.05 .mcdTable continues on next page1MRS757464 C Section 2Modbus data mappingsREM611 21Point List Manual