2.4.1.32 LD0.MPTTR1 Thermal overload protection for motors (1)Table 74:LD0.MPTTR1 Thermal overload protection for motors (1)RegA Type Scale IEC 61850 name SA name Description ValuesLD0.MPTTR1147 u16 1 .TmpRl.mag.f Therm-lev Thermal level 0.00...9.99148 i16 1 .TmpUsed.mag.f TEMP_AMB Ambient temperature -99...999 [C]149 u16 10 .ThmLevSt THERMLEV_ST Start therm.level 0.00...9.99150 u16 10 .ThmLevEnd THERMLEV_END End therm.level 0.00...9.99151 u16 1 .BlkThmRsTm.stVal T_ENARESTART Est. time to reset block restart 0...99999 [s]2.4.1.33 LD0.RESCMMXU1 Residual current demand value (1)Table 75:LD0.RESCMMXU1 Residual current demand value (1)RegA Type Scale IEC 61850 name SA name Description ValuesLD0.RCAVMMXU1 Demand value1989 u16 1000 .A.res.cVal.mag.f I_DMD_RES Residual amplitude 0.00…50.0[×In]1990 Year - month1991 Day - hour1992 Minute - second1993 Milliseconds1994 Time qualityLD0.RCMAMMXU1 Max. demand value1995 u16 1000 .A.res.cVal.mag.f Max demand Io Residual amplitude 0.00…50.0[×In]1996 Year - month1997 Day - hour1998 Minute - second1999 Milliseconds2000 Time qualityLD0.RCMIMMXU1 Min. demand valueu16 1000 .A.res.cVal.mag.f Min demand Io Residual amplitude 0.00…50.0[×In]2.4.1.34 LD0.RESCMMXU1 Residual current measurement (1)Table 76:LD0.RESCMMXU1 Residual current measurement (1)RegA Type Scale IEC 61850 name SA name Description ValuesLD0.RESCMMXU1 Residual current (1)141 u16 1000 .A.res.instCVal.mag.f I0_INST - amplitude0.00...40.0[×In]Section 2 1MRS757464 CModbus data mappings48 REM611Point List Manual