RegA Type Scale IEC 61850 name SA name Description Values9406 u16 1 Minute, second Min/Sec9407 u16 1 Millisecond Millisecond9408 u16 1 Timestamp quality2.4.1.13 Fault record dataThe table shows all potential data available in the fault record application. Which datais actually recorded depends on the functions available and enabled in the IEDconfiguration.Table 55:Fault record dataRegA Type Scale IEC 61850 name 1) SA name Description ValuesLD0.FLTRFRC1 Fault record data9409 u32 1 .OpCnt.stVal Fault record number (high) 0..9999999410 (Low word)9411 i16 1 .ProFcn.stVal Protection function -32768...327679412 u16 100 .Hz.mag.f Frequency 30…80.00[Hz]9413 u16 100 .StrDur.mag.f Start duration 0...100.00 [%]9414 u32 1000 .StrOpTm.mag.f Operate time [ms] (high) 0...999999.9999415 (Low word)9416 u32 100 .FltPtR.mag.f Fault resistance 0.00…1000000.00ohms9417 (Low word)9418 u32 100 .FltDiskm.mag.f Fault distance 0.00…9999.99 pu9419 (Low word)9420 u16 1 .ActSetGr.stVal Active setting group 1…69421 u16 1 .ShotPntr.stVal AR shot pointer value 0...7Captured values during fault9422 u16 1000 .Max50DifAA.mag.f Max. diff. current phs A 0.000...80.000 [pu]9423 u16 1000 .Max50DifAB.mag.f Max. diff. current phs B 0.000...80.000 [pu]9424 u16 1000 .Max50DifAC.mag.f Max. diff. current phs C 0.000...80.000 [pu]9425 u16 1000 .Max50RstAA.mag.f Max. bias current phs A 0.000…50.000 [pu]9426 u16 1000 .Max50RstAB.mag.f Max. bias current phs B 0.000…50.000 [pu]9427 u16 1000 .Max50RstAC.mag.f Max. bias current phs C 0.000…50.000 [pu]Table continues on next page1MRS757464 C Section 2Modbus data mappingsREM611 35Point List Manual