4.12.3.9 Monitored dataTable 982:HCUBPTOC Monitored dataName Type Values (Range) Unit DescriptionSTART_DUR FLOAT32 0.00...100.00 % Ratio of start time /operate timeI_NAT_AMPL_A FLOAT32 0.00...5.00 xIn Recorded naturalunbalance currentamplitude phase AI_NAT_ANGL_A FLOAT32 -179.00...179.00 deg Recorded naturalunbalance current anglephase AI_NAT_AMPL_B FLOAT32 0.00...5.00 xIn Recorded naturalunbalance currentamplitude phase BI_NAT_ANGL_B FLOAT32 -179.00...179.00 deg Recorded naturalunbalance current anglephase BI_NAT_AMPL_C FLOAT32 0.00...5.00 xIn Recorded naturalunbalance currentamplitude phase CI_NAT_ANGL_C FLOAT32 -179.00...179.00 deg Recorded naturalunbalance current anglephase CI_COM_AMPL_A FLOAT32 0.00...5.00 xIn Compensated unbalancecurrent amplitude phaseAI_COM_ANGL_A FLOAT32 -179.00...179.00 deg Compensated unbalancecurrent angle phase AI_COM_AMPL_B FLOAT32 0.00...5.00 xIn Compensated unbalancecurrent amplitude phaseBI_COM_ANGL_B FLOAT32 -179.00...179.00 deg Compensated unbalancecurrent angle phase BI_COM_AMPL_C FLOAT32 0.00...5.00 xIn Compensated unbalancecurrent amplitude phaseCI_COM_ANGL_C FLOAT32 -179.00...179.00 deg Compensated unbalancecurrent angle phase CHCUBPTOC Enum 1=on2=blocked3=test4=test/blocked5=offStatusIL1-unb:1 FLOAT32 0.00...5.00 xIn Measured unbalancecurrent amplitude phaseAIL2-unb:1 FLOAT32 0.00...5.00 xIn Measured unbalancecurrent amplitude phaseBIL3-unb:1 FLOAT32 0.00...5.00 xIn Measured unbalancecurrent amplitude phaseC1MRS759142 C Section 4Protection functionsREX640 1043Technical Manual