Table 1278:PEMMXU Non group settings (Advanced)Parameter Values (Range) Unit Step Default DescriptionForward Wh Initial 0...999999999 1 0 Preset Initial value for forward activeenergyReverse Wh Initial 0...999999999 1 0 Preset Initial value for reverse activeenergyForward VArh Initial 0...999999999 1 0 Preset Initial value for forward reactiveenergyReverse VArh Initial 0...999999999 1 0 Preset Initial value for reverse reactiveenergyMeasurement mode 1=PhsA, PhsB,PhsC2=Arone3=Pos Seq4=PhsAB5=PhsBC6=PhsCA7=PhsA8=PhsB9=PhsC1=PhsA, PhsB,PhsCSelected measurement mode for powercalculationPulse on time 0.050...60.000 s 0.001 1.000 Energy accumulated pulse ON time insecsPulse off time 0.050...60.000 s 0.001 0.500 Energy accumulated pulse OFF time insecs8.1.12.7 Monitored dataTable 1279:PEMMXU Monitored dataName Type Values (Range) Unit DescriptionS-kVA:1 FLOAT32 -999999.9...999999.9kVA Total Apparent PowerP-kW:1 FLOAT32 -999999.9...999999.9kW Total Active PowerQ-kVAr:1 FLOAT32 -999999.9...999999.9kVAr Total Reactive PowerPF:1 FLOAT32 -1.00...1.00 Average Power factorRSTACM BOOLEAN 0=False1=TrueReset of accumulatedenergy readingS_INST FLOAT32 -999999.9...999999.9kVA Apparent power,magnitude ofinstantaneous valueS_DB FLOAT32 -999999.9...999999.9kVA Apparent power,magnitude of reportedvalueS_DMD FLOAT32 -999999.9...999999.9kVA Demand value ofapparent powerP_INST FLOAT32 -999999.9...999999.9kW Active power, magnitudeof instantaneous valueP_DB FLOAT32 -999999.9...999999.9kW Active power, magnitudeof reported valueTable continues on next pageSection 8 1MRS759142 CMeasurement functions1330 REX640Technical Manual