Module DescriptionBIO1001/BIO1003 14 × BI + 8 × SOBIO1002/BIO1004 6 × SPO + 2 × SPO (TCS) + 9 × BIRTD1001 10 × RTD channels + 2 × mA channels (input/output)AIM1001 4 × CT + 1 × CT (sensitive, for residual current only) + 5 × VTAIM1002 6 × CT + 4 × VTSIM1001 3 × combi sensor inputs + 1 × CT (sensitive, for residual current only) + 1 × VTPSM1001 24...60 VDC, 3 × PO (TCS) + 2 × PO + 3 × SO + 2 × SSOPSM1002 48...250 VDC / 100...240 VAC, 3 × PO (TCS) + 2 × PO + 3 × SO + 2 × SSOPSM1003 110/125 VDC (77...150 VDC), 3 × PO (TCS) + 2 × PO + 3 × SO + 2 × SSOPO = Power OutputSO = Signal OutputSPO = Static Power OutputSSO = Static Signal Output1) Line distance/line differential protection communication + binary signal transfer, optical multimode orsingle-mode LC small form-factor pluggable transceiver (SFP)The relay has a nonvolatile memory which does not need any periodical maintenance.The nonvolatile memory stores all events, recordings and logs to a memory whichretains data if the relay loses its auxiliary supply.2.3 Local HMIThe LHMI is used for setting, monitoring and controlling the protection relay and therelated process. It comprises a 7-inch color screen with capacitive touch sensing anda Home button at the bottom of the LHMI.The LHMI must be paired with the protection relay to enable all thefunctionalities in it. See the operation manual for the pairingprocedure.The LHMI is an accessory for the relay which is fully operational evenwithout the LHMI.Section 2 1MRS759142 CREX640 overview62 REX640Technical Manual