The sum of the numbers in column “Value when activated” when all OUTx(1≤x≤16) are active equals 65535. This is the highest integer that can be convertedby the ITBGAPC function block.10.11 Elapsed time integrator with limit transgression andoverflow supervision TEIGAPC10.11.1 Identification GUID-1913E066-37D1-4689-9178-5B3C8B029815 v3Function Description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2 devicenumberElapsed time integrator TEIGAPC - -10.11.2 Application GUID-B4B47167-C8DE-4496-AEF1-5F0FD1768A87 v2The function TEIGAPC is used for user-defined logics and it can also be used fordifferent purposes internally in the IED. An application example is the integrationof elapsed time during the measurement of neutral point voltage or neutral currentat earth-fault conditions.Settable time limits for warning and alarm are provided. The time limit foroverflow indication is fixed to 999999.9 seconds.10.11.3 Setting guidelines GUID-2911D624-87D5-4427-BB2F-E0D1072394FA v3The settings tAlarm and tWarning are user settable limits defined in seconds. Theachievable resolution of the settings depends on the level of the values defined.A resolution of 10 ms can be achieved when the settings are defined within therange1.00 second ≤ tAlarm ≤ 99 999.99 seconds1.00 second ≤ tWarning ≤ 99 999.99 seconds.If the values are above this range, the resolution becomes lower due to the 32 bitfloat representation99 999.99 seconds < tAlarm ≤ 999 999.0 seconds99 999.99 seconds < tWarning ≤ 999 999.0 secondsNote that tAlarm and tWarning are independent settings, that is,there is no check if tAlarm > tWarning.1MRK 505 383-UEN A Section 10LogicBreaker protection REQ650 2.2 IEC 209Application manual