Function block with defined functions for autorecloser indications in monitordirection, I103AR. This block includes the FUNCTION TYPE parameter, and theINFORMATION NUMBER parameter is defined for each output signal.Measurands M17109-99 v2The measurands can be included as type 3.1, 3.2, 3.3, 3.4 and type 9 according tothe standard.• Measurands in public rangeFunction block that reports all valid measuring types depending on connectedsignals, I103Meas.• Measurands in private rangeFunction blocks with user defined input measurands in monitor direction,I103MeasUsr. These function blocks include the FUNCTION TYPE parameter foreach block in the private range, and the INFORMATION NUMBER parameter foreach block.Fault location M17109-108 v1The fault location is expressed in reactive ohms. In relation to the line length inreactive ohms, it gives the distance to the fault in percent. The data is available andreported when the fault locator function is included in the IED.Disturbance recordings M17109-111 v9• The transfer functionality is based on the Disturbance recorder function. Theanalog and binary signals recorded will be reported to the master by polling.The eight last disturbances that are recorded are available for transfer to themaster. A file that has been transferred and acknowledged by the mastercannot be transferred again.• The binary signals that are included in the disturbance recorder are those thatare connected to the disturbance function blocks B1RBDR to B22RBDR.These function blocks include the function type and the information numberfor each signal. For more information on the description of the Disturbancereport in the Technical reference manual. The analog channels, that arereported, are those connected to the disturbance function blocks A1RADR toA4RADR. The eight first ones belong to the public range and the remainingones to the private range.14.6.2 Settings M17109-116 v1Section 14 1MRK 505 383-UEN AStation communication278 Breaker protection REQ650 2.2 IECApplication manual