2.3.1.2 CTRL.CBCILO1 Circuit breaker enable signals (1)Table 5:CTRL.CBCILO1 Circuit breaker enable signals (1)BitA RegA IEC 61850 name SA name Description ValuesCTRL.CBCILO12824 176.08 .EnaOpn.stVal ENA_OPEN Open enabled 1=Enabled2825 176.09 .EnaCls.stVal ENA_CLOSE Close enabled 1=Enabled2.3.1.3 CTRL.CBCSWI1 Circuit breaker (1) mom. positionTable 6:CTRL.CBCSWI1 Circuit breaker (1) mom. positionBitA RegA IEC 61850 name SA name Description ValuesCTRL.CBCSWI1 POSITION2804 175.04 .Pos.stVal.Close - Close bit 1=Close2805 175.05 .Pos.stVal.Open - Open bit 1=Open2806 175.06 .Pos.stVal.Fault - Fault bit 1=Pos(00/11)2834 177.02 .SynItlByps.stVal ITL_BYPASS Interlock bypass 1=Bypass2835 177.03 .mcd2.3.1.4 CTRL.CBCSWI1 Circuit breaker (1) mom+mcd positionTable 7:CTRL.CBCSWI1 Circuit breaker (1) mom+mcd positionBitA RegA IEC 61850 name SA name Description ValuesCTRL.CBCSWI1 POSITION2816 176.00 .Pos.stVal.Close Close bit 1=Close2817 176.01 .mcd2818 176.02 .Pos.stVal.Open Open bit 1=Open2819 176.03 .mcd2820 176.04 < reserved >2821 176.05 < reserved >2822 176.06 .Pos.stSeld SELECTED CB selected for control 1=Selected2823 176.07 .mcd2.3.1.5 CTRL.CBXCBR1 Circuit-breaker control (1)Table 8:CTRL.CBXCBR1 Circuit-breaker control (1)BitA RegA IEC 61850 name SA name Description ValuesCTRL.CBXCBR12836 177.04 .BlkOpn.stVal BLK_OPEN Open blocked 1=Blocked2837 177.05 .mcdTable continues on next pageSection 2 1MRS756878 HModbus data mappings18 RET615Point List Manual