little meaning, since it is always possible to redefine the settings completely for theuser-definable register.2.4.2.1 CTRL.LLN0 Local, Remote, Station, Off and CombinationsTable 155:CTRL.LLN0 Local, Remote, Station, Off and CombinationsRegA Type Scale IEC 61850 name SA name Description ValuesCTRL.LLN0u16 1 .LocKeyHMI.stVal0=Off; 1=Loc; 2=Rem; 3=Stat;4=L+R; 5=L+S; 6=L+S+R; 7=S+R 0…72.4.2.2 LD0.FMMXU1 Frequency measurement (1)Table 156:LD0.FMMXU1 Frequency measurement (1)RegA Type Scale IEC 61850 name SA name Description ValuesLD0.FMMXU1u16 100 .Hz.mag F_DB Frequency35.00...75.00[Hz]2.4.2.3 LD0.LLN0/LPHD1/LDEV1 System valuesTable 157:LD0.LLN0/LPHD1/LDEV1 System valuesRegA Type Scale IEC 61850 name SA name Description ValuesLD0.LLN0u16 1 .ParChgCnt.stVal Num. of setting changes 0…655352.4.2.4 LD0.MDSOPT1 Runtime counter for machines and devices (1)Table 158:LD0.MDSOPT1 Runtime counter for machines and devices (1)RegA Type Scale IEC 61850 name SA name Description ValuesLD0.MDSOPT1u16 1 .OpTmh.stVal OPR_TIME Total operation hours 0…2999992.4.2.5 LD0.MVI4GAPC1 Integer value move (1)Table 159:LD0.MVI4GAPC1 Integer value move (1)RegA Type Scale IEC 61850 name SA name Description ValuesLD0.MVI4GAPC1i32 1 .ISCS01.stVal OUT1 - Integer value 1 (high)-/+2147483647- Low wordTable continues on next pageSection 2 1MRS756878 HModbus data mappings82 RET615Point List Manual