2.4.1.34 LD0.PEMMTR1 Three-phase energy measurementsTable 137:LD0.PEMMTR1 Three-phase energy measurementsRegA Type Scale IEC 61850 name SA name Description ValuesLD0.PEMMTR12100 u32 1 .SupWh.actVal Reverse active energy (high)0..1E10[kWh]2101 .SupWh.actVal (low word)2102 u32 1 .SupVArh.actVal Reverse reactive energy (high)0..1E10[kVArh]2103 .SupVArh.actVal (low word)2104 u32 1 .DemWh.actVal Forward active energy (high)0..1E10[kWh]2105 .DemWh.actVal (low word)2106 u32 1 .DemVArh.actVal Forward reactive energy (high)0..1E10[kVArh]2107 .DemVArh.actVal (low word)2.4.1.35 LD0.PEMMXU1 Power measurement demand values (1)Table 138:LD0.PEMMXU1 Power measurement demand values (1)RegA Type Scale IEC 61850 name SA name Description ValuesLD0.PEAVMMXU1 Demand value1939 i32 1 .TotW.mag Active power P (high) -/+ 999,9991940 (Low word)1941 i32 1 .TotVAr.mag Reactive power Q (high) -/+ 999,9991942 (Low word)1943 i32 1 .TotVA.mag Apparent power S (high) -/+ 999,9991944 (Low word)1945 i16 1000 .TotPF.mag Power factor -1…1LD0.PEMAMMXU1 Max demand valuei32 1 .TotW.mag Active power P -/+ 999,999i32 1 .TotVAr.mag Reactive power Q -/+ 999,999i32 1 .TotVA.mag Apparent power S -/+ 999,999LD0.PEMIMMXU1 Min demand valuei32 1 .TotW.mag Active power P -/+ 999,999i32 1 .TotVAr.mag Reactive power Q -/+ 999,999i32 1 .TotVA.mag Apparent power S -/+ 999,9991MRS756878 H Section 2Modbus data mappingsRET615 75Point List Manual