BitA RegA IEC 61850 name SA name Description Values3265 204.01 .mcd.mom-only Mom only alternative3266 204.02 .SPCSO2.stVal X130-Output 2 State 0/1=Off/On3267 204.03 .mcd.mom-only Mom only alternative3268 204.04 .SPCSO3.stVal X130-Output 3 State 0/1=Off/On3269 204.05 .mcd.mom-only Mom only alternative2.3.1.73 LD0.XRGGIO130 Alarm/warningTable 76:LD0.XRGGIO130 Alarm/warningBitA RegA IEC 61850 name SA name Description ValuesLD0.XRGGIO1303032 189.08 .Alm.stVal - XRGGIO130 Alarm 1=Alarm3033 189.09 .mcd3034 189.10 .Wrn.stVal - XRGGIO130 Warning 1=Warning3035 189.11 .mcd2.3.2 Unmapped indicationsUnmapped indications are indication data that have no initial Modbus mappinglocations, but can be added to the user-definable Modbus area using theCommunication Management tool in PCM600. If Modbus events are enabled forthese indication signals, the event identification is the user-definable area address.2.3.2.1 All premapped three-phase protection function stages, operate/phase-dependent objects addedTable 77:All premapped three-phase protection function stages, operate/phase-dependent objects addedBitA RegA IEC 61850 name SA name Description ValuesLD0.xxxxxxxx (various).Op.phsA Phs A operate 1 = Operate.mcd.Op.phsB Phs B operate 1 = Operate.mcd.Op.phsC Phs C operate 1 = Operate.mcdSection 2 1MRS756878 HModbus data mappings46 RET615Point List Manual