Table 5.1.18.-2 Warning codes (Continued)Fault Weight valueDNP 3.0 configuration error b) 16DNP 3.0 module faulty 32∑ 63a) The external fault warning can be routed to SO2 with SGF1/8.b) Can be corrected by restoring factory settings for DNPFor further information on warnings, refer to the Operator’s Manual.5.1.19. Relay parameterizationThe parameters of the relay can be set either locally via the HMI or externally viaserial communication with Relay Setting Tool.Local parameterizationWhen the parameters are set locally, the setting parameters can be chosen via thehierarchical menu structure. The wanted language can be selected for parameterdescriptions. Refer to the Operator’s Manual for further information.External parameterizationRelay Setting Tool is used for parameterizing the relay units. Adjusting theparameter values using Relay Setting Tool is done off-line, after which theparameters can be downloaded to the relay via a communication port.5.2. Design description5.2.1. Input/output connectionsAll external circuits are connected to the terminals on the rear panel of the relay.* Terminals X2.1-_ are dimensioned for one 0.5...6.0 mm 2 wire or two max 2.5mm 2 wires* Terminals X3.1-_ and X4.1-_ are dimensioned for one 0.2...2.5 mm 2 wire or two0.2...1.0 mm2 wires.The energizing phase-to-phase voltages of the relay are connected to terminals:* X2.1/1-2* X2.1/3-4* X2.1/5-6For inputs for phase-to-phase voltages and residual voltage, refer to Table 5.2.1.-1.104REU 610 Voltage RelayTechnical Reference Manual1MRS755769