41/18-77 EN BP7_ CTRL_PARP7.0 KP UP KP value, up 1.0...100.0 - 5.0P7.1 KP DN KP value, down 1.0...100.0 - 5.0P7.2 TV UP TV value, up 0...1000 msec 200P7.3 TV DN TV value, down 0...1000 msec 200P7.4 GOPLS UP Go pulse, up 0...200 msec 0P7.5 GOPLS DN Go pulse, down 0...200 msec 0P7.6 Y-OFS UP Y offset, up Y-Min...100.0 % 24.0P7.7 Y-OFF DN Y offset, down Y-Min...100.0 % 24.0P7.8 not used not used not used - -P7.9 TOL_BAND Tolerance band X...10.20 % 0.30P7.10 TEST Test Action - -P7.11 EXIT Return to operat. level Action - -P8._ , P9._ P.10_ not used not usedP11._ FS / IPP11.0 FAIL_POS Safe position ACTIVE, INACTIVE - INACTIVEP11.1 FACT_SET Factory setting Action - -P11.2 IP_TYP I/P module type NO_F_POS, F_SAFE_1, F_SAFE_2, F_FREEZE1, F_FREEEZE_2 - NO_F_POSP11.3 EXIT Return to operat. level Action - -Par. Display Function Parameter setting Unit Factory setting