Installing and commissioning41/18-77 EN Installing and commissioning 53.1.2 Operating conditions at the installation siteAmbient temperature: -40 ... +85 °C (-40 ... +185 °F)Relative humidity < 75% (95% for a short time), non-condensingObserve the specifications for protection classIP65 / NEMA 4XExplosion protection: Observe the specifications in the certificate, see section“Certificates” on page 29.Mounting position: any orientation allowed, provided that the splash guardcap is in place, see section “Mounting the splash guardcap” on page 15.3.1.3 Mounting to linear actuatorsA special attachment kit is available for mounting the positioner to a linear actuatoraccording to DIN/IEC 534 (lateral mounting to NAMUR) comprising the following parts:Tools required: Wrench 10 mm/13 mmAllen key 4 mm• Lever (1.0) w. followerpin, for 10...35 mm or25...90 mm actuatorstroke• Follower guide (2.0)with two screws (2.1)and clamp plates (2.2)• Angle bracket (3.0)with two screws (3.1),two spring washers(3.2), and two plainwashers (3.3)• Screw (3.4) and plainwasher (3.5) formounting to cast ironyoke• Two U-bolts (3.7),each with two nuts(3.8), two springwashers (3.9), andtwo plain washers(3.10) for mounting tocolumnar yokeBefore installing check to ensure that the specifications in terms of safetyand control applicable to the TZID-C110 will not be exceeded.Warning3.43.53.73.103.83.1 3.2 3.33.02.12.22.01.03.9