41PP-32KOOLMASTER PP-32 REV.015.8 HEATER SETTINGSThe PP-32 operates up to eight independent heater stages. A start andstop temperature is defined for each heating stage. The stop temperaturemust be at least 0.5°F (0.3°C) greater than the start temperature for agiven heater and the start temperature cannot be greater than the setpoint. The number of heater stages needed and the sensor assignment foreach stage is determined during the installation (see sec. 5.14.3 and5.14.4). The following diagram shows the operation of an heater stage.Start and stop temperatures of all heater stages can be set separatelyfor summer and winter seasons. Refer to sec. 5.2.2 to select the properseason.Set the function to "10. Temp. Settings" from the main menu usingthe navigation buttons. The current set point is displayed.Press the down-arrow key to selectthe start or stop temperature of thedesired heater stage.Use the adjustment buttons to setthe Start or Stop temperature to the desired value.Proceed in similar fashion for both winter and summer seasons.Refer to sec. 5.2.2 to select the proper season.2 X22UH ,pG2r2R2y 2222UV H@Ar2R2y..222UW H@AONROOM T°OFFHEATER HEATERTURNS ONHEATERTURNS OFFOPERATION OF HEATER STAGES