58PP-32KOOLMASTER PP-32 REV.01Adjusting the Open-Time for the Hi Static Pressure AlarmThe Open-Time of the tunnel curtain or vent doors, in case a Hi staticpressure alarm occurs, can be adjusted from 0 to 900 sec.Set the function to "21.Alarm Limits" from the main menu usingthe navigation buttons.Use the navigation buttons to select "2.Static Pressure" then pressthe right-arrow key.Press the right-arrow key onceagain in order to select the "3.HiStatic Alarm" option. The openingtime of vent doors and of the tunnelcurtain are displayed.Use the adjustment buttons to adjust vents doors' Open-Time.Press the down-arrow key once to select curtain's Open-Time.Use the adjustment buttons to adjust curtain's Open-Time.5.13.3 Resetting the Alam LogResetting the alarm log can only be performed from the installer mode.Set the function to "19.Installation" from the main menu using thenavigation buttons then press the right-arrow key. The "ClearAlarms" menu is selected. Note that this menu is only accessiblefrom the installer mode (see sec. 5.14.2).Use the adjustment buttons to select "Yes", in order to clear thealarm log. The answer is validated after an 8 second delay or whenthe user exits the menu.r 2 2e+y 2 22222QHy 2 +2222QH