Installation and Commissioning Guide - Split Ducted ESP Digital UnitsDoc. No.0525-077 Ver. 2 200129Installation and Commissioning Guide Split Ducted ESP Digital1407.05. SRD203CUNIT MODELNUMBERUNITWEIGHT(kg)CORNER WEIGHTS (kg)A B C DSRD203C 196 46.8 54.2 8.6 86.4OVERALL NOMINAL DIMENSION (H X W X L)= 1045 X 1460 X 580PLEASE NOTE THAT UNDER ALL CIRCUMSTANCES,CONDENSER AIR MUST NOT RECIRCULATE BACK ONTOCONDENSER COIL. KEEP ALL CLEARANCES FREE OFANY OBSTRUCTIONS1460 O/A355 525580O/A2551045O/A575980517(MTG C-C DIST)9101005(MTG C-C DIST)67195(MTG C-C DIST)270108110 11557.5303525 25585FRONT VIEWSIDE VIEWTOP VIEW55340 500MINIMUM SERVICE ACCESS AREASAND AIRFLOW CLEARANCESHEIGHT CLEARANCE= 1500 mmA BC D600 mmSERVICECLEARANCE(COMPRESSORANDELECTRICALS)400 mmSERVICE / AIRFLOW CLEARANCENIL - TO - MINIMUM SERVICE CLEARANCEOUTDOOR COILCOMP300 mmSERVICE / AIRFLOWCLEARANCENOTES:1. Do not scale drawing. All dimensions are in mm unless specified. Referto corresponding unit dimensional drawing for mounting hole details.2. Service Access Areas and Spaces for Airflow Clearances given above aresuggested minimum based on the condition that the spaces around theunits are free from any obstructions and a walkway passage of 1000mmbetween the units or between the unit and the outside perimeter isavailable.3. Minimum service access areas and spaces for airflow clearances areresponsibilities of the installer, ActronAir will not be held liable for anyextra charges incurred due to lack of access and space for airflow.4. Under all circumstances, condenser air must not recirculate back ontocondenser coil. Keep all clearance free of any obstructions.5. Maximum External Static of Outdoor Fans is 5 Pa.6. STACKING OF UNITS: Ensure that minimum airflow and clearances aremet.7. Refer to Pipe Connection Details on Specifications Sheet.8. MTG C-C DIST = Mounting Centre to Centre Distance.9. Use M12 bolt for feet mounting.THIRD ANGLEPROJECTION