Installation and Commissioning Guide - Split Ducted ESP Digital UnitsDoc. No.0525-077 Ver. 2 200129Installation and Commissioning Guide Split Ducted ESP Digital32Copyright © 2007 ActronAir. All rights reserved. 0500-050Ver. 02Auto Heat Cool Mode Operation Time ChartShowing Cooling to Heating change over.SET TEMPTIME(SET TEMP - 4)(SET TEMP + 4)ROOM TEMP( C)COMPRESSORAMBIENTTEMP. WARMER COOLERCooling(MODULATING 10 - 100%)Cooling(100%) OFF Heating(MODULATING)(SET TEMP - 1)R410A Pressure / Temperature ChartTempo CPressureKPaTempo CPressureKPaTempo CPressureKPaTempo CPressureKPa-60 -34.4 -28 194.9 4 805.9 36 2090.7-59 -30.7 -27 206.9 5 834.1 37 2145.5-58 -26.8 -26 219.2 6 862.9 38 2201.3-57 -22.8 -25 231.9 7 892.6 39 2258.2-56 -18.6 -24 245.1 8 922.8 40 2316.1-55 -14.2 -23 258.7 9 953.8 41 2375.1-54 -9.6 -22 272.6 10 985.4 42 2435.1-53 -4.8 -21 286.9 11 1017.8 43 2496.2-52 0.8 -20 301.7 12 1050.9 44 2558.5-51 5.3 -19 316.9 13 1084.7 45 2621.8-50 10.7 -18 332.6 14 1119.2 46 2686.2-49 16.3 -17 348.7 15 1154.6 47 2751.8-48 22.2 -16 365.2 16 1190.7 48 2818.5-47 28.2 -15 382.3 17 1227.5 49 2886.4-46 34.0 -14 399.7 18 1265.2 50 2955.5-45 40.9 -13 417.7 19 1303.6 51 3025.7-44 47.8 -12 436.2 20 1342.9 52 3097.2-43 54.8 -11 455.1 21 1382.9 53 3169.9-42 62.1 -10 474.6 22 1423.9 54 3243.7-41 69.6 -9 494.6 23 1465.7 55 3318.9-40 77.4 -8 515.1 24 1508.3 56 3395.2-39 85.5 -7 536.2 25 1551.8 57 3472.9-38 93.9 -6 557.8 26 1596.2 58 3551.8-37 102.5 -5 579.9 27 1641.4 59 3631.9-36 111.5 -4 602.6 28 1687.6 60 3713.5-35 120.8 -3 625.9 29 1734.6 61 3796.3-34 130.4 -2 649.8 30 1782.6 62 3880.5-33 140.3 -1 674.3 31 1831.6 63 3965.9-32 150.5 0 699.4 32 1881.5 64 4052.8-31 161.1 1 724.9 33 1932.3 65 4140.9-30 171.9 2 751.3 34 1984.1 66 4230.6-29 183.3 3 778.3 35 2036.9 67 4321.5R-410A Pressure / Temperature Chart