Control Wiring 5-9MN762S5.3.4 User PI Control Mode (P1-07 = 4)Table 5-6 Parameter P1-08 Control of Digital Inputs when P1-07=4P1-08 Digital In 1(Term 2)Digital In 2(Term 3)Digital In 3(Term 4)Analog Input(Term 6)0, 2, 4, 6,9, 13, 16,18Open: StopClosed: Run No Function No FunctionBipolar analoginput(No Function)3 Open: Stop Open: Forward Open: Modbus Speed ref Bipolar analoginputClosed: Run Closed: Reverse Closed: Preset Speed 1 ref (No Function)5Open: StopClosed: RunOpen: Modbus SpeedClosed: Preset SpeedDigital Input 3(Term 4)BipolarAnalog Input(Term 6)Preset SpeedOpen Open Preset Speed 1Closed Open Preset Speed 2Open Closed Preset Speed 3Closed Closed Preset Speed 410Open: StopClosed: RunOpen: Master Speed refClosed: Digital Speed refExternal trip input Bipolar analoginput(No Function)Open: TripClosed: No Trip11Open: StopClosed: RunOpen: Master Speed refClosed: Preset Speed 1External trip input Bipolar analoginput(No Function)Open: TripClosed: No Trip12Open: StopClosed: RunOpen: Master Speed refClosed: Bipolar Analog refExternal trip input Bipolar analoginput(No Function)Open: TripClosed: No Trip17 Open: Stop Open: Master Speed ref Open: Modbus / Analog Ref Bipolar analoginputClosed: Run Closed: Bipolar Analog ref Closed: Preset Speed 1 (No Function)19 Open: Stop Open: Master Speed ref Analog Input 2Bipolar analoginputClosed: Run Closed: Analog Input 2 ref (No Function)20, 21 Open: Stop Digital Output: Open: Master Speed ref Bipolar analoginputClosed: Run Drive Healthy = +24V Closed: Preset Speed 1 (No Function)22 Open: StopClosed: RunDigital Output:Drive Healthy = +24VExternal trip input Bipolar analoginput(No Function)Open: TripClosed: No Trip