Parameter Descriptions 7-1MN762S7.1 OverviewParameters are presented in this Chapter and each setting is explained. Selecting P00 and pressingENT/PROG accesses a read-only menu to monitor internal drive values. Once in the display view, theUP and DOWN arrows will scroll between the read only variables shown in Tables 7-5 and 7-8.7.2 Basic ParametersTable 7-1 Basic Parameters - Parameter Group 1ParNo. Description Range Units Default ExplanationP1-01 Motor ratedvoltage 0, 20 to 600 Volts 575 Rated (nameplate) voltage ofthe motor (Volts).P1-02 Motor ratedcurrent25% -100% of driverated current Amps DriveratingEnter the rated (nameplate)current of the motor. This valueis used for overload protection.P1-03 Motor ratedfrequency 25Hz to 2000Hz Hz 60 Enter the rated (nameplate)frequency of the motor.P1-04 Motor ratedspeed 0 to 60 000 rpm Rpm 0When non-zero, all speedrelated parameters aredisplayed in rpm. Enter themotor rated (nameplate) speedif this is required.P1-05MinimumFrequency /Speed0.0 to P1-06 HzRpm 0.0Minimum speed limit – Hz orrpm.If P1-04 >0, the value enteredis in Rpm.P1-06MaximumFrequency /SpeedP1-05 to 5*P1-03(max 2000Hz)HzRpm 60.0Maximum speed limit – Hz orrpm.If P1-04 >0, the value enteredis in Rpm.P1-07Terminal /Keypad /PID / DriveControl ModeSelection0: Terminal control1: Keypad control –fwd only2: Keypad control –fwd and rev3: PID Control4: Modbus RTUControl- 0Primary Control Mode of thedrive.0: Terminal control1: Uni-directional keypadcontrol. Keypad STARTbutton does not reversedirection.2: Bi-directional keypadcontrol. Keypad STARTbutton toggles betweenforward and reverse.3: User PID control withexternal feedback signal.4: Modbus RTU Control.Chapter 7Parameter Descriptions