4017 - SpECIfIC DETaIlS fOR UNITS WITH a faNWITH avaIlaBlE STaTIC pRESSURE (30RQSY)Selection based on the pressure dropThe cooling and heating capacities are given for anavailable pressure of 160 Pa and for a unit without filter.To calculate the performances at other pressure dropsplease use the correction factors below.Cooling mode30RQSY 039-050/30RQSY 080-120Duct pressuredropfan speed, r/s power inputcoefficientCooling capacitycoefficient0 12.00 0.943 1.01950 13.33 0.962 1.012100 14.66 0.980 1.006130 15.46 0.990 1.003160 16.26 1.000 1.000200 17.31 1.012 0.998240 18.36 1.023 0.99630RQSY 060-078/30RQSY 140-160Duct pressuredropfan speed, r/s power inputcoefficientCooling capacitycoefficient0 15.83 0.929 1.01850 16.81 0.944 1.016100 17.78 0.964 1.014130 18.36 0.978 1.011160 18.36 1.000 1.000180 18.36 1.019 0.991Heating mode30RQSY 039-050/30RQSY 080-120Duct pressuredropfan speed, r/s power inputcoefficientHeating capacitycoefficient0 18.36 0.990 1.01650 18.36 0.990 1.012100 18.36 0.990 1.009130 18.36 1.000 1.005160 18.36 1.000 1.000200 18.36 1.000 0.994240 18.36 1.010 0.98130RQSY 060-078/30RQSY 140-160Duct pressuredropfan speed, r/s power inputcoefficientHeating capacitycoefficient0 18.36 1.000 1.02650 18.36 1.000 1.020100 18.36 1.000 1.011130 18.36 1.000 1.007160 18.36 1.000 1.000180 18.36 1.001 0.993Note:Pressure drop, clean filter = 6 PaPressure drop, dirty filter = 12 PaThis option permits the production of free hot water usingheat reclaim by desuperheating the compressor dischargegases. The option is available for the whole 30RQS/30RQSYrange.18 – paRTIal HEaT REClaIM USING DESUpER-HEaTERS (OpTION 49)A plate heat exchanger is installed in series with the aircondenser coils on the compressor discharge line of eachcircuit.The control configuration for the desuperheater option isfactory assembled.18.1 - physical data, 30RQS/30RQSY units with partial heat reclaim using desuperheaters (option 49)30RQS/RQSY partial heat reclaim mode 039 045 050 060 070 078 080 090 100 120 140 160Operating weight 30RQS units with RTpf coils*Standard unit without hydronic module kg 515 522 548 561 562 569 762 909 917 973 1088 1106Standard unit with hydronic module optionSingle high-pressure pump kg 544 552 578 591 591 599 792 941 949 1009 1127 1145Dual high-pressure pump kg 570 578 603 617 617 625 818 986 994 1057 1164 1155Operating weight 30RQSY units with RTpf coils*Standard unit without hydronic module kg 530 537 568 582 582 589 776 944 953 1008 1118 1135Standard unit with hydronic module optionSingle high-pressure pump kg 560 567 597 611 612 619 806 975 985 1044 1157 1174Dual high-pressure pump kg 586 593 623 637 638 645 832 1020 1030 1092 1194 1211Refrigerant charge, units with RTpf coils R410ACircuit A kg 12,5 13,5 16,5 17,5 18 16,5 21,5 27,5 28,5 33 19 18,5Circuit B kg - - - - - - - - - - 19 18,5Condensers Grooved copper tubes. aluminium finsDesuperheaters on circuits a and B Plate heat exchangersWater volume l 0,549 0,549 0,549 0,732 0,732 0,732 0,732 0,976 0,976 0,976 0,732 0,732Water volume l - - - - - - - - - - 0,732 0,732Max. water-side operating pressure without hydronicmodulekPa 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000Water connections Cylindrical, male gas threadConnections in 1 1 1 1 1 1 1 1 1 1 1 1Outside diameter mm 42 42 42 42 42 42 42 42 42 42 42 42* Weights shown are a guideline only.