8f. Refer to the outdoor unit Installation, Start-Up andService Instructions for additional information.g. Install a factory-supplied filter drier near the out-door unit. On heat pump systems, a bi-flow filterdrier must be used.3. Insulate and caulk wall openings to reduce air infiltra-tion and refrigerant pipe vibrations on structure.4. Evacuate piping, if necessary. If either refrigerant pip-ing or the indoor coil is exposed to atmospheric condi-tions, it must be evacuated to 1000 microns toeliminate contamination and moisture in the system.Step 5 — Connect Condensate Drain Line —Observe all local sanitary codes when installing condensatedrains. Refer to Fig. 3 and 14 for drain pipe connection fromindoor unit.1. Use hard polyvinyl chloride (PVC) pipe material withnominal ID of 3/4 in. to connect at drain line. Use pipeinsulation 1/4-in. thick, such as Armaflex insulation, onexposed piping inside the conditioned space.2. To ensure regular flow of condensate water, the drainpipe should be pitched toward an open drain or sumpat a downward slope of at least 1/4-in. per ft.3. Attach plate with screws under piping hole.4. Attach drain pipe with nylon wire tie passing throughhole (Fig. 15).NOTE: Do not fasten nylon wire ties tight enough todeform the insulation, as this affects its performance.5. Insulate condensate drain line(s) that are located in orabove an occupied area with a condensate-proof mate-rial such as polyurethane or neoprene.6. Install an external trap at the end of the condensateline.NOTE: Should the installation require one, a conden-sate pump may be ordered as a field-installedaccessory.Table 4A — Piston and Charge Combinations — Cooling Only SystemsTable 4B — Piston and Charge Combinations — Heat Pump Systems*Size 060 indoor heat pump systems use a TXV (thermostatic expansion valve), part no. EA36YD250.Table 4C — Piston and Charge Combinations — Heat and Cool Systems*Size 060 indoor heat pump systems use a TXV (thermostatic expansion valve), part no. EA36YD250.COOLINGINDOOR UNIT SIZEOUTDOOR UNIT38HDRPISTONSIZE CHARGE (lb)024 018 57 7.0024 57 7.75036 030 65 10.1036 70 8.9048 048 80 12.2060 060 90 12.5HEAT PUMPINDOOR UNIT SIZEOUTDOOR UNIT38QRRPISTON SIZEINDOORPISTON SIZEOUTDOOR CHARGE (lb)024 018 49 40 7.5024 55 43 7.8036 030 65 55 12036 70 63 13048 048 82 73 12.2060 060 —* 80 12.8HEAT PUMPINDOOR UNIT SIZE OUTDOOR UNIT38HDR PISTONSIZE CHARGE (lb)024 018 57 7.0024 57 7.75036 030 65 10.1036 70 8.9048 048 80 12.2060 060 —* 12.5