Electrical data (cont)50HX ELECTRIC HEATER PACKAGES — 208/240 V, SINGLE-PHASE,DUAL-POINT WIRING CONNECTIONSUNITSIZE50HXELECTRIC HEATACCESSORY KITCPHEATER---A00ELECTRIC HEAT(kW)* HEATERFLAMIN CIRCUITAMPACITY FORWIRE SIZINGMAX FUSEOR HACRBRKRMOCP208 V 240 V 208 V 240 V 208 V 240 V 208 V 240 V 208 V 240 V024001 3.75 5.0 18.1 20.8 22.5 26.0 25 30 — —002 5.60 7.5 27.1 31.3 33.7 39.1 35 40 — —015 7.50 10.0 36.1 41.7 45.1 50.8 50 60 — —030001 3.75 5.0 18.1 20.8 22.5 26.0 25 30 — —014 5.60 7.5 27.1 31.3 33.7 39.1 35 40 — —015 7.50 10.0 36.1 41.7 45.1 50.1 50 60 — —016 11.30 15.0 54.1 62.0 67.9 78.1 — — 70 80036001 3.75 5.0 18.1 20.8 22.5 26.0 25 30 — —014 5.60 7.5 27.1 31.3 33.7 39.1 35 40 — —015 7.50 10.0 36.1 41.7 45.1 50.8 50 60 — —016 11.30 15.0 54.3 62.5 67.9 78.1 — — 70 80042001 3.75 5.0 18.1 20.8 22.5 26.0 25 30 — —014 5.60 7.5 27.1 31.3 33.7 39.1 35 40 — —015 7.50 10.0 36.1 41.7 45.1 50.8 50 60 — —016 11.30 15.0 54.1 62.0 67.9 78.1 — — 70 80017 15.00 20.0 72.1 83.3 90.1 104.2 — — 100 110048013 3.75 5.0 18.1 20.8 22.5 26.0 25 30 — —014 5.60 7.5 27.1 31.3 33.7 39.1 35 40 — —015 7.50 10.0 36.1 41.7 45.1 50.8 50 60 — —016 11.30 15.0 54.1 62.0 67.9 78.1 — — 70 80017 15.00 20.0 72.1 83.3 90.1 104.2 — 100 110060013 3.75 5.0 18.1 20.8 22.5 26.0 25 30 — —014 5.60 7.5 27.1 31.3 33.7 39.1 35 40 — —015 7.50 10.0 36.1 41.7 45.1 50.8 50 60 — —016 11.30 15.0 54.1 62.0 67.9 78.1 — — 70 80017 15.00 20.0 72.2 83.3 90.1 104.2 — — 100 110LEGENDFLA — Full Load AmpsHACR BRKR — Heating, Air Conditioning and Refrigeration CircuitBreakerMOCP — Maximum Overcurrent Protection (fuses or HACR-type circuit breaker)NEC — National Electrical Code*Electric heat capacity (kW) is based on heater voltages of 208 v or240 v. If power distribution voltage to units varies from rated heatervoltage, see Wattage Multiplication Factors table on page 19.NOTE: In compliance with NEC requirements for multimotor and com-bination load equipment (refer to NEC Articles 430 and 440), the over-current protective device for the unit shall be fuse or HACR breaker.20