ARI* capacities (cont)OUTDOOR SOUND: ONE-THIRD OCTAVE BAND DATA — DECIBELSFREQ.HzUNIT 50HX024 030 036 042 048 06063 49.0 52.8 49.2 50.0 53.2 54.3125 60.7 59.2 62.3 64.7 65.4 65.1250 68.1 71.9 69.1 70.4 74.5 71.5500 69.3 69.7 70.9 69.9 74.3 72.71000 70.6 70.4 74.7 75.3 75.2 73.92000 68.8 68.8 69.3 73.8 72.6 73.44000 65.2 65.2 65.2 75.1 68.6 71.78000 59.4 57.1 58.3 69.2 61.2 66.3Physical dataUNIT 50HX 024 030 036 042 048 060REFRIGERANT R-22Refrigerant Control* Acutrol™ SystemSHIPPING WEIGHT (lb)Without Base Rail 309 340 368 368 411 425With Optional Base Rail 296 327 355 355 398 412COMPRESSOR Type ScrollINDOOR FAN Centrifugal — Direct DriveSpeeds 3 3 3 3 Variable VariableRpm (High Speed) 1075 1075 1100 1100 — —Diameter 10 10 10 10 10 10Width (in.) 9 9 9 9 10 10Nominal Airflow (Cfm) 800 1000 1300 1400 1600 1800Motor Hp 1⁄ 4 1 ⁄4 1 ⁄ 2 1 ⁄ 2 1.0 1.0INDOOR COILRows...Fins/in. 3...15 3...15 4...15 4...15 4...15 4...15Face Area (sq ft) 3.6 3.6 4.5 4.5 4.5 4.5OUTDOOR FAN Propeller — Direct DriveCfm 2200 2200 2200 2400 2400 2400Rpm 1100 1100 1100 1100 1100 1100Diameter (in.) 20 20 20 20 20 20Motor Hp 1⁄ 4 1 ⁄4 1 ⁄ 4 1 ⁄ 4 1 ⁄ 3 1 ⁄ 3OUTDOOR COILRows...Fins/in. 2...17 2...17 2...17 2...17 2...17 2...17Face Area (sq ft) 7.00 7.00 8.66 8.66 8.66 8.66FILTER SIZE (in.)†Throwaway 24 x 24 24 x 24 24 x 30 24 x 30 24 x 30 24 x 30*Operating charge listed on unit nameplate.†Recommended field-supplied filters are 1-in. thick.NOTE: Sizes 048 and 060 are equipped with an indoor integrated control motor (ICM).4