17LEGENDEwb – Entering Wet-BulbkW – Total Unit Power InputSHC – Sensible Heat Capacity (1000 Btuh)TC – Total Capacity (1000 Btuh) (net)NOTES:1. Ratings are net; they account for the effects of the evaporator-fan motor power and heat.2. Direct interpolation is permissible. Do not extrapolate.3. The following formulas may be used:sensible capacity (Btuh)t = t 2ldb edb 1.10 x cfmt = Wet-bulb temperature corresponding to enthalpy of air leavinglwb evaporator coil (h )lwbtotal capacity (Btuh)h = h 2lwb ewb 4.5 x cfmWhere: h = Enthalpy of air entering evaporator coilewbPerformance data (cont)ECONOMIZER 1-in. FILTER PRESSURE DROP (in. wg)MULTIPLICATION FACTORSExample: 15.0 kw (at 240v) heater on 208v= 15.0 (.75 mult factor)= 11.25 capacity at 208vUNIT50JZ PRESSURE DROP024-036 0.20042-060 0.25HEATER kwRATINGVOLTAGEDISTRIBUTION V/3/60MULTIPLICATIONFACTOR240200208230240.69.75.921.00480440460480.84.921.00LEGENDBF — Bypass FactorEwb — Entering Wet-BulbkW — Total Unit Power InputSHC — Sensible Heat Capacity (1000 Btuh)TC — Total Capacity (1000 Btuh) (net)Edb — Entering Dry-Bulbrh — Relative Humidity— Indicates Integrated Ratings4. The SHC is based on 80°F edb temperature of air entering evaporatorcoil. Below 80°F edb, subtract (corr factor x cfm) from SHC.Above 80°F edb, add (corr factor x cfm) to SHC.Correction Factor = 1.10 x (1 + BF) x (edb + 80).5. Integrated capacity is maximum (instantaneous) capacity less the effectof frost on the outdoor coil and the heat required to defrost it.NOTES:1. Ratings are net; they account for the effectsof the evaporator-fan motor power and heat.2. Direct interpolation is permissible. Do not extrapolate.3. The following formulas may be used:ELECTRIC HEAT PRESSURE DROP TABLESSmall Cabinet: 024-036Large Cabinet: 042-060STATIC CFM500 600 700 800 900 1000 1100 1200 1300 1400 1500 16005 Kw 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.02 0.04 0.06 0.0710 Kw 0.00 0.00 0.00 0.00 0.00 0.02 0.04 0.06 0.07 0.09 0.10 0.1115 Kw 0.00 0.00 0.00 0.02 0.04 0.06 0.08 0.10 0.12 0.14 0.16 0.1820 Kw 0.00 0.00 0.02 0.04 0.06 0.08 0.09 0.11 0.13 0.15 0.17 0.19STATIC CFM1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 25005 Kw 0.00 0.00 0.00 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.10 0.11 0.1210 Kw 0.00 0.00 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.10 0.11 0.12 0.1315 Kw 0.00 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.10 0.11 0.12 0.13 0.14 0.1520 Kw 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.10 0.11 0.12 0.13 0.14 0.15 0.16