7Base unit dimensions—50JZ024-036REQ’D CLEARANCES FOR OPERATION AND SERVICING. IN. (MM)EVAPORATOR COIL ACCESS SIDE . . . . . . . . . . . . . 36 (914)POWER ENTRY SIDE (EXCEPT FOR NEC REQUIREMENTS) . . 36 (914)UNIT TOP. . . . . . . . . . . . . . . . . . . . . . . . . . 48 (1219)SIDE OPPOSITE DUCTS . . . . . . . . . . . . . . . . . . . 36 (914)DUCT PANEL . . . . . . . . . . . . . . . . . . . . . . . 12 (304.8)**MINIMUM DISTANCES: IF UNIT IS PLACED LESS THAN 12 IN. (304.8 MM) FROMWALL SYSTEM, THEN THE SYSTEM PERFORMANCE MAY BE COMPROMISED.REQ’D CLEARANCES TO COMBUSTIBLE MAT’L. IN. (MM)TOP OF UNIT . . . . . . . . . . . . . . . . . . . . . . . 14 (355.6)DUCT SIDE OF UNIT. . . . . . . . . . . . . . . . . . . . . 2 (50.8)SIDE OPPOSITE DUCTS . . . . . . . . . . . . . . . . . . 14 (355.6)BOTTOM OF UNIT . . . . . . . . . . . . . . . . . . . . . 0.50 (12.7)ELECTRIC HEAT PANEL . . . . . . . . . . . . . . . . . . 36 (914.4)NEC REQ’D CLEARANCES. IN. (MM)BETWEEN UNITS, POWER ENTRY SIDEUNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDEUNIT AND BLOCK OF CONCRETE WALLS AND OTHERGROUNDED SURFACES, CONTROL BOX SIDE. . . . . . . . . . 42 (1066.8). . 36 (914). . . . . . . 42 (1066.8)LEGENDCG - CENTER OF GRAVITYCOND - CONDENSEREVAP - EVAPORATORNEC - NATIONAL ELECTRICAL CODEREQ'D - REQUIREDNOTE: DIMENSIONS ARE IN IN. (MM)4 4 . 5 [ 1 . 7 5 ]UNIT ELECTRICALCHARACTERISTICSUNIT WEIGHT UNIT HEIGHTin. [mm]“A”CENTER OF GRAVITYin. [mm]lb kg X Y Z50JZ024 208/230-1-60 299 135.6 35.02 [889.5] 19.0 [482.6] 18.3 [463.6] 16.0 [406.4]50JZ030 208/230-1-60, 208/230-3-60 320 145.2 37.02 [940.3] 20.0 [508.0] 19.3 [489.0] 17.6 [447.0]50JZ036 208/230-1-60, 208/230-3-60, 460-3-60 328 148.8 37.02 [940.3] 20.0 [508] 19.0 [482.6] 16.5 [419.1]50JZ 024-036 Dimensions