REQUIRED CLEARANCES TO COMBUSTIBLE MATERIAL — in. (mm)Unit Top . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 (356)Duct Side of Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 (51)Side Opposite Ducts . . . . . . . . . . . . . . . . . . . . . . . . 14 (356)Bottom of Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0Vertical Discharge First 12 in. (305) of Supply Duct . . . . . . . 1 (25)NECESSARY REQUIRED CLEARANCES — in. (mm)Between Units, Control Box Side . . . . . . . . . . . . . . . . 42 (1067)Unit and Ungrounded Surfaces, Control Box Side . . . . . . 36 (914)Unit and Block or Concrete Walls and Other GroundedSurfaces, Control Box Side . . . . . . . . . . . . . . . . . . . 42 (1067)REQUIRED CLEARANCES FOR SERVICING — in. (mm)Evaporator Coil Access Side . . . . . . . . . . . . . . . . . . . 30 (762)Control Box Access Side . . . . . . . . . . . . . . . . . . . . . . 30 (762)(Except for Necessary Requirements)Unit Top . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 (914)Side Opposite Ducts . . . . . . . . . . . . . . . . . . . . . . . . 30 (762)NOTES:1. Clearances must be maintained to prevent recirculation of air fromoutdoor-fan discharge.2. Dimensions in ( ) are in millimeters.UNIT50SXCENTER OF GRAVITY (in./mm)X Y Z024 21.7/552 20.7/527 12.7/321030 21.9/556 20.7/525 12.7/321036 20.8/528 20.0/507 12.7/321LEGENDCG — Center of Gravity NEC — National Electrical CodeCOND — Condenser REQ’D — RequiredMAT’L — MaterialUNIT50SXELECTRICALCHARACTERISTICSUNIT WT CORNER WT (Lb/Kg)Lb Kg A B C D024 208/230-1-60 270 123 67/30 62/28 99/45 42/19030 208/230-1-60 273 124 66/30 64/29 100/45 43/20036 208/230-1-60, 208/230-3-60, 460-3-60 291 132 80/36 54/25 112/51 45/20Fig. 6 — Dimensions; Units 50SX024-036 Without Base Rail6