T-365 4–56P5-1 Supply Probe Test This test if for units equipped with secondary supply probe only.The temperature difference between primary supply probe and secondarysupply probe is compared.Test passes if temperature comparison falls within the specified range.NOTICEIf this test fails, “P5-1” and “FAIL” will be displayed. If bothProbe tests (this and the SUPPLY/RETURN TEST) pass,because of the multiple tests, the display will read “P 5”“PASS.”P5-2 Return Probe Test For units equipped with secondary return probe only.The temperature difference between return temperature sensor (RTS) andreturn temperature sensor (RRS) probe is compared.Test passes if temperature comparison falls within the specified range.NOTICE1. If this test fails, “P5-2” and “FAIL” will be displayed. If bothProbe tests (this test and the SUPPLY/RETURN) pass,because of the multiple tests, the display will read “P 5,”“PASS.”2. The results of Pre-trip tests 5-0, 5-1 and 5-2 will be used toactivate or clear control probe alarms.P5-3 Evaporator Fan Di-rection TestWith evaporator fan running on high speed, measure the temperature differ-ence between the primary supply and primary return probes. Turn the heat-ers on for 60 seconds then measure the temperature difference between theprimary supply and primary return probes for up to 120 additional seconds.This is a Pass/Fail test. The test passes if differential of STS is 0.25°C higherthan RTS.Test P5-0 must pass before this test is run.P5-7 Primary vs Sec-ondary EvaporatorTemperature Sen-sor TestThis is a Pass/Fail test of the primary evaporator temperature sensor (ETS1)and secondary evaporator temperature sensor (ETS2).Test passes if secondary evaporator temperature sensor (ETS2) is within +/- 0.5°C of the primary evaporator temperature sensor (ETS1).P5-8 Primary Evapora-tor Pressure Trans-ducer TestThis is a Pass/Fail test of the Primary Evaporator Pressure Transducer.Test passes if suction pressure transducer (SPT) is within +/- 0 psi of satura-tion pressure at current evaporator temperature. Also passes if SPT is within+/- 1 psi of discharge pressure 6 hours after a power interruption.Test P5-7 must pass before this test is run.P5-9 Suction (Evapora-tor) PressureTransducer TestUnits equipped with a secondary Evaporator pressure transducer.Test passes if suction pressure transducer (SPT) is within +/- 1.5 psi of theevaporator pressure transducer (EPT).Test P5-8 must pass before this test is run.CODE TITLE DESCRIPTION