11Table 8B — 23XRV Additional Data for Condenser Marine Waterboxes**Add to heat exchanger data for total weights or volumes.NOTES:1. Weight adder shown is the same for cooler and condenser of equal frame size.2. For the total weight of a vessel with a marine waterbox, add these values to the heat exchanger weights (or volume).Table 9A — 23XRV Waterbox Cover Weights — English (lb)*Rows with two entries list nozzle end and return end weights.Table 9B — 23XRV Waterbox Cover Weights — SI (kg)LEGEND*Rows with two entries list nozzle end and return end weights.NOTE: Weight for NIH 2-pass cover, 150 psig (1034 kPa), is included in the heat exchanger weights shown in Table 7.RIG MACHINE COMPONENTS — Refer to Fig. 10-26 andCarrier Certified Prints for machine component disassembly.NOTE: Label each wire before removal when wiring must bedisconnected (see Fig. 10 and 11). Clip all wire ties necessarywhen removing pressure and temperature sensors. Disconnectall pressure transducer wires at the sensor. Temperature sensorscannot be disconnected from their cables; remove temperaturesensors from their thermowells and label as required.HEAT EXCHANGERFRAME, PASSENGLISH SIPsig Rigging Weight(lb) (see Note 2)Water Volume(gal) kPa Rigging Weight(kg) (see Note 2)Water Volume(L)FRAME 3, 1 AND 3 PASS 150 N/A N/A 1034 N/A N/AFRAME 3, 2 PASS 150 365 42 1034 166 159FRAME 4, 1 AND 3 PASS 150 N/A N/A 1034 N/A N/AFRAME 4, 2 PASS 150 989 54 1034 449 204FRAME 5, 1 AND 3 PASS 150 N/A N/A 1034 N/A N/AFRAME 5, 2 PASS 150 1195 60 1034 542 227FRAME 3, 1 AND 3 PASS 300 N/A N/A 2068 N/A N/AFRAME 3, 2 PASS 300 430 42 2068 195 159FRAME 4, 1 AND 3 PASS 300 N/A N/A 2068 N/A N/AFRAME 4, 2 PASS 300 1641 47 2068 744 178FRAME 5, 1 AND 3 PASS 300 N/A N/A 2068 N/A N/AFRAME 5, 2 PASS 300 1909 50 2068 866 189WATERBOXDESCRIPTIONCOOLER CONDENSERFrame 3 Frame 4 Frame 5 Frame 3 Frame 4 Frame 5VictaulicNozzles Flanged VictaulicNozzles Flanged VictaulicNozzles Flanged VictaulicNozzles Flanged VictaulicNozzles Flanged VictaulicNozzles FlangedNIH,1 pass Cover 150 PSIG 282 318 148 185 168 229 282 318 148 185 168 229NIH,2 pass Cover 150 PSIG 287 340 202 256 222 276 287 340 191 245 224 298NIH,3 pass Cover 150 PSIG 294 310 472 488 617 634 294 310 503 519 628 655NIH Plain End, 150 PSIG 243 243 138 138 154 154 225 225 138 138 154 154MWB End Cover, 150 PSIG* 243/315 243/315 138/314 138/314 154/390 154/390 225/234 225/234 138/314 138/314 154/390 154/390NIH,1 pass Cover 300 PSIG 411 486 633 709 764 840 411 486 633 709 764 840NIH,2 pass Cover 300 PSIG 411 518 626 733 760 867 411 578 622 729 727 878NIH,3 pass Cover 300 PSIG 433 468 660 694 795 830 433 468 655 689 785 838NIH Plain End, 300 PSIG 291 291 522 522 658 658 270 270 522 522 658 658MWB End Cover, 300 PSIG* 445/619 445/619 522/522 522/522 658/658 658/658 359/474 359/474 522/522 522/522 658/658 658/658WATERBOXDESCRIPTIONCOOLER CONDENSERFrame 3 Frame 4 Frame 5 Frame 3 Frame 4 Frame 5VictaulicNozzles Flanged VictaulicNozzles Flanged VictaulicNozzles Flanged VictaulicNozzles Flanged VictaulicNozzles Flanged VictaulicNozzles FlangedNIH,1 pass Cover 150 PSIG 128 144 67 84 76 104 128 144 67 84 76 104NIH,2 pass Cover 150 PSIG 130 154 92 116 101 125 130 154 87 111 102 135NIH,3 pass Cover 150 PSIG 133 141 214 221 280 288 133 141 228 235 285 297NIH Plain End, 150 PSIG 110 110 63 63 70 70 102 102 63 63 70 70MWB End Cover, 150 PSIG 110/143 110/143 63/142 63/142 70/177 70/177 102/106 102/106 63/142 63/142 70/177 70/177NIH,1 pass Cover 300 PSIG 186 220 287 322 347 381 186 220 287 322 346 381NIH,2 pass Cover 300 PSIG 186 235 284 332 344 393 186 235 282 331 330 398NIH,3 pass Cover 300 PSIG 196 212 299 315 361 376 196 212 297 313 356 380NIH Plain End, 300 PSIG 132 132 237 237 298 298 122 122 237 237 298 298MWB End Cover, 300 PSIG 202/281 202/281 237/237 237/237 298/298 298/298 163/215 163/215 237/237 237/237 298/298 298/298NIH — Nozzle-in-HeadMWB — Marine WaterboxIMPORTANT: Only a qualified service technicianshould perform this operation.Do not attempt to disconnect flanges while the machine isunder pressure. Failure to relieve pressure can result inpersonal injury or damage to the unit.Before rigging the compressor remove control panel andcontrol center.