9Table 3 — 23XRV Dimensions (Marine Waterbox)*Assumes both cooler and condenser nozzles on same end of chiller.†1 or 3 pass length applies if cooler is a 1 or 3 pass design.NOTES:1. Service access should be provided per American Society of Heating, Refrigeration, and Air Conditioning Engineers(ASHRAE) 15, latest edition, National Fire Protection Association (NFPA) 70, and local safety code.2. Allow at least 3 ft (915 mm) overhead clearance for service rigging for frame R compressor.3. Certified drawings available upon request.4. Marine waterboxes may add 6 in. to the width of the machine. See certified drawings for details.5. ‘A’ length and ‘B’ width dimensions shown are for standard 150 psi design and victaulic connections. The 300 psi design and/or flanges will add length. See certified drawings.Table 4 — 23XRV Waterbox Nozzle SizesTable 5 — 23XRV Compressor Weights*Compressor weight is comprised of compressor, stator, rotor, and end bell.Table 6 — 23XRV Component Weights — TR Compressor*To determine compressor frame size, refer to Fig. 2.HEAT EXCHANGERSIZEA (Length, Marine Waterbox — not shown) MAXIMUMB WIDTHMAXIMUMC HEIGHT2-Pass* 1 or 3 Pass†ft-in. mm ft-in. mm ft-in. mm ft-in. mm30 to 32 14- 9 4496 16-4 3 / 4 4997 6-9 3 /8 2067 7-2 5 /8 220035 to 37 16- 5 1 / 2 5017 18-1 1 / 4 5518 6-9 3 /8 2067 7-2 5 /8 220040 to 42 15- 2 3 / 4 4642 16-81 / 4 5086 6-9 3 / 4 2076 7-6 1 / 2 229945 to 47 16-11 1 / 4 5163 18-4 3 / 4 5607 6-9 3 / 4 2076 7-6 1 / 2 229950 to 52 15- 3 1 / 2 4661 16-81 / 2 5093 7-1 2159 7-6 3 / 4 230555 to 57 17- 0 5182 18-5 5613 7-1 2159 7-63 / 4 2305FRAMESIZEPRESSUREpsig (kPa) PASS NOMINAL PIPE SIZE (in.) ACTUAL PIPE ID (in.)Cooler Condenser Cooler Condenser3 150/300(1034/2068)1 10 10 10.020 10.0202 8 8 7.981 7.9813 6 6 6.065 6.0654 150/300(1034/2068)1 10 10 10.020 10.0202 8 8 7.981 7.9813 6 6 6.065 6.0655 150/300(1034/2068)1 10 10 10.020 10.0202 8 10 7.981 10.0203 6 8 6.065 7.981MOTORCODEENGLISH SITotal CompressorWeight*(lb)Total CompressorWeight*(kg)P4866 2207QRSTUVCOMPONENTFRAME 3HEAT EXCHANGER*FRAME 4HEAT EXCHANGER*FRAME 5HEAT EXCHANGER*lb kg lb kg lb kgSuction Elbow 179 81 237 108 232 105Discharge Pipe Assembly 747 339 747 339 747 339Control Center 1650 749 1650 749 1650 749Discharge Pipe Adapter Flange 178 81 178 81 178 81Optional Isolation Valves 70 32 70 32 115 52Optional Unit Mounted Pumpout Unit 164 75 164 75 164 75Vaporizer Oil Sump 700 318 700 318 700 318Economizer 542 246 542 246 542 246