10Table 6 — Quick Access ChartLEGEND NOTES:1. To change from Edit mode to Status mode, press or pressagain.2. Not all available selections will have items to select in sublevels.Automatic Run Test — The 50BV,XJ unit controls areprogrammed with an automatic run test that checks connectionand operation of major components. To perform the run test:Verify that the control display (LID device/System Monitor)interface cable is connected to internal jack on main controller;that the fire alarm/shutdown switch input (FSD) has a factoryjumper or field input; that Bypass (if installed) is set in theDRIVE position; and that the Local/Off/Remote switch is set tothe REMOTE position.NOTE: When the Local/Off/Remote switch is in theREMOTE position, the controller time schedule is pre-set(from the factory) as unoccupied. This means that the unitwill not turn on until the run test is enabled. However, if thecontroller schedule has already been modified in the field,and the current time of day is occupied, then the supply fanwill start. The run test will shut the fan down when itbegins. The run test will complete and then the supply willautomatically restart.NOTE: If the Local/Off/Remote switch is in the OFF posi-tion, it is normal for the red alarm light on the display panelto be lit, indicating that the unit is disabled.NOTE: If the red light stays on when the switch is moved toREMOTE, or if any other problems occur during the runtest, refer to the Troubleshooting section of this manual.To perform the Run Test:1. Turn unit power on.The LID display will show the controller identifica-tion, time and date (Fig. 5):OMNIZONE VPAChh:mm mm-dd-yyLIDNUM.KEYLID FUNCTION KEYSAlgorithms(ALGO)Status(STAT)History(HIST)Service(SRVC)Alarm(ALRM)Setup(SET)Schedules(SCHD)1 AO—Adaptive Control Hardware Points Alarm History Function Definition Limit Set Clock Occupancy2 AO—Cooling CV Software Points Analog Point Trace Channel Definition Setpoint Real Time Clock Setpoint3 AO—Cooling VAV Temperature Input Discrete Point Trace System Definition Discrete Controller Password Holiday4 AO—Fan Tracking Milliamp Input Consumable Channel Setpoint Definition First out N/A S/W Setpoint5 AO—Heating CV Custom Milliamp Input Internal Consumable Database Control Runtime N/A Network Time6 AO—Heating VAV Voltage Input Runtime Channel Comfort Controller # of starts N/A N/A7 AO—Humidity Control Custom Voltage Input N/A CCN Control N/A N/A N/A8 AO—Mixed Air CV w/IAQ Sensed Discrete Input N/A LID Preferences N/A N/A N/A9 AO—Mixed Air VAV w/IAQ Latched Discrete Input N/A N/A N/A N/A N/A10 AO—Permissive Interlock Pulsed Discrete Input N/A N/A N/A N/A N/A11 AO—Reset Milliamp Output N/A N/A N/A N/A N/A12 AO—Shared Transducer Custom Milliamp Output N/A N/A N/A N/A N/A13 AO—Static Pressure Voltage Output N/A N/A N/A N/A N/A14 DO—Analog Custom Voltage Output N/A N/A N/A N/A N/A15 DO—DX-Staging VAV Discrete Output N/A N/A N/A N/A N/A16 DO—Electric Heat CV Stepper Motor Output N/A N/A N/A N/A N/A17 DO—Electric Heat VAV Discrete Software Point N/A N/A N/A N/A N/A18 DO—Enthalpy Comparison Analog Software Point N/A N/A N/A N/A N/A19 DO—Interlock Network Data Out N/A N/A N/A N/A N/A20 DO—Lighting Control Network Data In N/A N/A N/A N/A N/A21 DO—Permissive Interlock N/A N/A N/A N/A N/A N/A22 DO—Pump Control N/A N/A N/A N/A N/A N/A23 DO—Prop Thermo N/A N/A N/A N/A N/A N/A24 DO—Prop Thermo 2 Pipe N/A N/A N/A N/A N/A N/A25 DO—Prop Thermo 4 Pipe N/A N/A N/A N/A N/A N/A26 DO—Staged Thermostat N/A N/A N/A N/A N/A N/A27 DO—Staging Control N/A N/A N/A N/A N/A N/A28 DO—Time Clock N/A N/A N/A N/A N/A N/A29 DO—Time Clock w/Check N/A N/A N/A N/A N/A N/A30 AOSS Schedule N/A N/A N/A N/A N/A N/A31 Network Broadcast N/A N/A N/A N/A N/A N/A32 Linkage/AOSS Schedule N/A N/A N/A N/A N/A N/A33 NTFC w/Enthalpy Check N/A N/A N/A N/A N/A N/A34 Sensor Group N/A N/A N/A N/A N/A N/A35 WSM Air Source N/A N/A N/A N/A N/A N/A36 WSM Cool Source N/A N/A N/A N/A N/A N/A37 Custom Program N/A N/A N/A N/A N/A N/AAO — Analog OutputAOSS — Adaptive Optimal Start/StopCV — Constant VolumeDO — Digital OutputIAQ — Indoor Air QualityN/A — Not AvailableNTFC — Nighttime Free CoolingVAV — Variable Air VolumeWSM — Water System ManagerCLEAREXPN/EDIT