58Configuration Screens (cont)*Default values from factory.NOTE: See CC6400 Comfort Controller Overview and Configuration Manual for configuration information.Maintenance ScreensDESCRIPTION VALUE* UNITS NAMEOMNIZONE::VPTESTC: Field TestField TestReschedule Rate 5 sec RESCHRATPower on Delay 40 sec RESCHPOROMNIZONE::MODECTRC: Mode ControlDetermines HeatReschedule Rate 10 sec RESCHRATPower on Delay 30 sec RESCHPORRun Fan in BypassReschedule Rate 10 sec RESCHRATPower on Delay 30 sec RESCHPORWater Economizer ControlReschedule Rate 10 sec RESCHRATPower on Delay 30 sec RESCHPORMod Valve & EconoReschedule Rate 2 sec RESCHRATPower on Delay 10 sec RESCHPOROMNIZONE::SETSYNCC: Setpoint SynchronizationSetpoint SynchReschedule Rate 3 sec RESCHRATPower on Delay 10 sec RESCHPORDESCRIPTION VALUE UNITS STATUS FORCE NAMEOMNIZONE::ADAPT01: VAVRESET Software point controlAnalog Output Point 0 % ValueStatus Point Off ValueOccupied ? No StatusReset Point 0 dF ValueControlling Setpoint 0 dF RefOutControl Point 0 dF ValuePID_Master_LoopReference Output 0 % RefOutProportional Term 0 % PTermIntegral Term 0 % ITermDerivative Term 0 % DTermIntegrator Flags 100 FlagsTask Timer 6 sec TaskTimrOMNIZONE::ADAPT02: Head Pressure controlAnalog Output Point 100 % Control ValueStatus Point Off Control ValueOccupied ? No StatusReset Point 0 PSIG ValueControlling Setpoint 0 PSIG RefOutControl Point 117.72 PSIG ValuePID_Master_LoopReference Output 0 % RefOutProportional Term 0 % PTermIntegral Term 0 % ITermDerivative Term 0 % DTermIntegrator Flags 100 FlagsTask Timer 2 sec TaskTimrOMNIZONE::ADAPT03: Building Pressure Ctrl.Analog Output Point 0 % ValueStatus Point Off ValueOccupied ? No StatusReset Point 0 ma ValueControlling Setpoint 12.32 ma RefOutControl Point 12.44 ma ValuePID_Master_LoopReference Output 0 % RefOutProportional Term 2 % PTermIntegral Term 0 % ITermDerivative Term 0 % DTermIntegrator Flags 100 FlagsTask Timer 3 sec TaskTimr