14Table 7 — Controller Set PointsLEGENDCheck System Parameters — To check systemparameters, press the button. The LID display willshow: “Hardware Points Table 1.” Press to view thehardware points. The user can navigate up and down throughthe points with the up and down arrows.Press 2 and to display the software points. The usercan navigate up and down through the points with the up anddown arrows.Refer to Tables 8 and 9 for hardware and software points.Display Alarm History — If the controller is indicatingthere are alarms, the user can view the alarm history bypressing the button. The LID display will show “AlarmHistory.” Press . The LID display will show the dateand type of alarm.As an example, if the LID display shows:ALARM — 10:55 11-27-02SFSThat display indicates that on 11/27/02 at 10:55 A.M. thesystem Supply Fan was either on when it had not beencommanded on or was off when it was commanded on.The user can view other stored alarms by pressing the upand down arrows. The twenty-four most recent alarms arestored.Configure Custom Programming Selections —To configure the custom programming selections, perform thefollowing procedure:1. Press 37 . The LID display will show:Custom Program2. Press . The LID display will show:2.0 Global DictionaryOMNIZONE3. Press . The display indicates “No Data.”Press then press . Pressagain. The LID display should now show:Compressor Stages4.004. Press 4 and then to indicate that 4 compressorsare installed.5. Use the down and up arrows to select the other configura-tion parameters as required. See Table 10 for a list of con-figuration parameters.6. A field-supplied 0 to 10 vdc signal to the 50XJ unit maybe used to reset the supply-air temperature.The reset will be taken off the supply air set pointconfigured in the controller. The reset range can bechanged by adjusting the High Conversion Endpointvalue of the custom voltage input to a value other than20. For example for 10 degrees of reset change the Hiinput value to 10. This may be found by pressing 7from the Keypad. RESET will be the secondcustom voltage input point in the controller. The firstwill be CSMUX, which is the compressor status multi-plexed input. Press to see the following in theLID display:Ext. Supply Air ResetRESETPress . If the LID display shows:System ValuePress . The LID display will show:Low Input Endpoint2.0 VoltsPress three times to get to the High ConversionEndpoint. The user must be logged in to be able to change thisotherwise you can only view it. See the start up section for howto log into the controller.Configuration parameters are shown in Table 10.DESCRIPTIONDISPLAYSCREENSVALUE UNITS STATUS FORCE NAMEOMNIZONE::SETPT01:Supply fan StatusOccupied Lo Setpoint 0.3 in H2O OccLowOccupied Hi Setpoint 0.4 in H2O OccHghUnoccupied Lo Setpoint 0.3 in H2O UnOccLowUnoccupied Hi Setpoint 0.4 in H2O UnOccHghOMNIZONE::SETPT02:VAVRESETbaselineOccupied Lo Setpoint 0 dF OccLowOccupied Hi Setpoint 0 dF OccHghUnoccupied Lo Setpoint 0 dF UnOccLowUnoccupied Hi Setpoint 0 dF UnOccHghOMNIZONE::SETPT03:Heat\Cool Mode & ResetOccupied Lo Setpoint 70 dF OccLowOccupied Hi Setpoint 74 dF OccHghUnoccupied Lo Setpoint 55 dF UnOccLowUnoccupied Hi Setpoint 85 dF UnOccHghOMNIZONE::SETPT04:Head Pressure ControlOccupied Lo Setpoint 225 PSIG OccLowOccupied Hi Setpoint 225 PSIG OccHghUnoccupied Lo Setpoint 225 PSIG UnOccLowUnoccupied Hi Setpoint 225 PSIG UnOccHghOMNIZONE::SETPT05:Supply Static PressureOccupied Lo Setpoint 1.5 in H2O OccLowOccupied Hi Setpoint 1.5 in H2O OccHghUnoccupied Lo Setpoint 1.5 in H2O UnOccLowUnoccupied Hi Setpoint 1.5 in H2O UnOccHghOMNIZONE::SETPT06:Supply Air TemperatureOccupied Lo Setpoint 55 dF OccLowOccupied Hi Setpoint 55 dF OccHghUnoccupied Lo Setpoint 55 dF UnOccLowUnoccupied Hi Setpoint 55 dF UnOccHghOMNIZONE::SETPT07:Building Static PressureOccupied Lo Setpoint 0.02 in H2O OccLowOccupied Hi Setpoint 0.02 in H2O OccHghUnoccupied Lo Setpoint 0.02 in H2O UnOccLowUnoccupied Hi Setpoint 0.02 in H2O UnOccHghOMNIZONE::SETPT08:BSP raw controlOccupied Lo Setpoint 12.32 ma OccLowOccupied Hi Setpoint 12.32 ma OccHghUnoccupied Lo Setpoint 12.32 ma UnOccLowUnoccupied Hi Setpoint 12.32 ma UnOccHghOMNIZONE::SETPT09:Humidity ControlOccupied Lo Setpoint 0 %RH OccLowOccupied Hi Setpoint 99 %RH OccHghUnoccupied Lo Setpoint 0 %RH UnOccLowUnoccupied Hi Setpoint 99 %RH UnOccHghBSP — Building Static PressureRH — Relative HumiditySTATENTERSTATHISTENTERALGOENTERENTERCLEAR EXPN/EDITENTERENTERSTATENTEREXPN/EDIT