41Table 20 – COOLING CAPACITIES 1--STAGE COOLING 6 TONS48TC07 (6 TONS) --- UNIT WITH HUMIDI---MIZER SYSTEM IN SUBCOOLING MODEAir Entering Evaporator --- CFMTemp (F) Air EntCondenser (Edb)80 dry bulb 80 dry bulb 80 dry bulb72 wet bulb 67 wet bulb 62 wet bulb2100 2400 2700 2100 2400 2700 2100 2400 270075TC 86.7 89.9 92.8 79.3 82.3 84.9 71.9 74.6 77.0SHC 40.1 41.8 43.3 46.9 48.5 49.9 53.7 55.2 56.5kW 4.3 4.3 4.3 4.2 4.2 4.2 4.2 4.2 4.285TC 79.5 82.6 85.4 72.5 75.3 77.9 65.4 68.0 70.3SHC 32.1 34.0 35.7 40.7 42.5 44.1 49.4 51.0 52.5kW 5.0 5.0 5.0 5.0 5.0 5.0 4.9 4.9 4.995TC 72.4 75.3 78.1 65.6 68.3 70.8 58.8 61.3 63.6SHC 24.1 26.3 28.1 34.6 36.6 38.3 45.1 46.9 48.5kW 5.8 5.8 5.8 5.7 5.7 5.7 5.6 5.6 5.6105TC 65.2 68.1 70.7 58.7 61.4 63.8 52.3 54.7 56.8SHC 16.2 18.5 20.5 28.5 30.6 32.6 40.7 42.8 44.6kW 6.5 6.5 6.5 6.4 6.4 6.4 6.3 6.3 6.3115TC 58.0 60.8 63.3 51.9 54.4 56.7 45.7 48.0 50.1SHC 8.2 10.7 13.0 22.3 24.7 26.8 36.4 38.6 40.6kW 7.2 7.2 7.2 7.1 7.1 7.1 7.0 7.0 7.048TC07 (6 TONS) --- UNIT WITH HUMIDI---MIZER SYSTEM IN HOT GAS REHEAT MODEAir Entering Evaporator --- CFMTemp (F) Air EntCondenser (Edb)75 dry bulb 75 dry bulb 75 dry bulb62.5 wet bulb (50% relative) 64 wet bulb (55% relative) 65.3 wet bulb (60% relative)2100 2400 2700 2100 2400 2700 1750 2000 270080TC 16.7 19.8 22.5 18.8 21.9 24.7 16.2 19.4 26.7SHC 0.6 0.6 0.6 --- 0.4 --- 0.4 --- 0.4 --- 1.3 --- 1.3 --- 1.3kW 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.075TC 17.7 20.6 23.1 19.6 22.6 25.3 17.3 20.3 27.1SHC 0.6 0.6 0.6 --- 0.3 --- 0.3 --- 0.3 --- 1.2 --- 1.2 --- 1.2kW 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.070TC 18.6 21.3 23.7 20.5 23.3 25.8 18.3 21.1 27.6SHC 0.7 0.7 0.7 --- 0.2 --- 0.2 --- 0.2 --- 1.0 --- 1.0 --- 1.0kW 4.0 4.0 4.0 4.1 4.1 4.1 4.1 4.1 4.160TC 20.5 22.9 25.0 22.2 24.7 26.8 20.4 22.8 28.5SHC 0.7 0.7 0.7 --- 0.0 --- 0.0 --- 0.0 --- 0.7 --- 0.7 --- 0.7kW 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.150TC 22.4 24.4 26.2 24.0 26.0 27.9 22.4 24.5 29.3SHC 0.8 0.8 0.8 0.1 0.1 0.1 --- 0.4 --- 0.4 --- 0.4kW 4.1 4.1 4.1 4.1 4.1 4.1 4.2 4.2 4.240TC 24.3 25.9 27.4 25.7 27.4 28.9 24.5 26.3 30.2SHC 0.8 0.8 0.8 0.3 0.3 0.3 --- 0.1 --- 0.1 --- 0.1kW 4.1 4.1 4.1 4.2 4.2 4.2 4.2 4.2 4.2LEGENDEdb --- Entering Dry--- BulbEwb --- Entering Wet--- BulbkW --- Compressor Motor Power InputIdb --- Leaving Dry--- BulbIwb --- Leaving Wet--- BulbSHC --- Sensible Heat Capacity (1000 Btuh) GrossTC --- Total Capacity (1000 Btuh) GrossNOTES:1. Direct interpolation is permissible. Do not extrapolate.2. The following formulas may be used:tldb = tedb – sensible capacity (Btuh)1.10 x cfmtlwb = Wet--- bulb temperature corresponding to enthalpy of airleaving evaporator coil (h lwb)h lwb = h ewb – total capacity (Btuh)4.5 x cfmWhere: h ewb = Enthalpy of air entering evaporator coil