60FAN PERFORMANCE (cont.)Table 37 – 48TC**04 3 PHASE 3 TON HORIZONTAL SUPPLYCFMAVAILABLE EXTERNAL STATIC PRESSURE (in. wg)0.2 0.4 0.6 0.8 1.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHPField Supplied Drive 1 Standard Static Option Medium Static Option900 553 0.14 681 0.22 782 0.32 870 0.42 948 0.53975 575 0.16 700 0.25 801 0.35 888 0.46 965 0.571050 597 0.18 720 0.28 820 0.38 906 0.49 983 0.611125 620 0.21 741 0.31 839 0.42 925 0.54 1001 0.661200 643 0.23 762 0.34 859 0.46 944 0.58 1020 0.711275 667 0.27 783 0.38 879 0.50 963 0.63 1038 0.761350 691 0.30 805 0.42 900 0.55 983 0.68 1057 0.821425 715 0.34 827 0.47 920 0.60 1002 0.74 1076 0.881500 740 0.38 849 0.52 941 0.66 1023 0.80 1096 0.95CFMAVAILABLE EXTERNAL STATIC PRESSURE (in. wg)1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHPMedium Static Option High Static Option900 1019 0.64 1084 0.76 1146 0.89 1203 1.02 1258 1.16975 1036 0.69 1101 0.81 1162 0.94 1219 1.08 1274 1.221050 1053 0.74 1118 0.86 1179 1.00 1236 1.14 1290 1.281125 1071 0.79 1135 0.92 1196 1.06 1253 1.20 1307 1.351200 1089 0.84 1153 0.98 1213 1.12 1270 1.27 1324 1.421275 1107 0.90 1171 1.04 1231 1.19 1287 1.34 1341 1.501350 1126 0.96 1189 1.11 1249 1.26 1305 1.42 1358 1.581425 1144 1.03 1208 1.18 1267 1.34 1323 1.50 1376 1.661500 1163 1.10 1226 1.25 1285 1.41 1341 1.58 1394 1.75NOTE: For more information, see General Fan Performance Notes.1. Recommend using field supplied drive (part no. KR11AG006) and belt (part no. KR30AE039)Table 38 – 48TC**04 3 PHASE 3 TON VERTICAL SUPPLYCFMAVAILABLE EXTERNAL STATIC PRESSURE (in. wg)0.2 0.4 0.6 0.8 1.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHPField Supplied Drive 1 Standard Static Option Medium Static Option900 567 0.15 688 0.22 786 0.30 871 0.37 947 0.44975 591 0.17 710 0.26 807 0.34 891 0.42 966 0.491050 615 0.20 732 0.29 828 0.38 911 0.47 985 0.551125 641 0.23 755 0.33 849 0.42 931 0.52 1005 0.611200 666 0.26 778 0.37 871 0.47 952 0.57 1025 0.671275 693 0.29 802 0.41 893 0.53 974 0.63 1046 0.741350 719 0.33 826 0.46 916 0.58 995 0.70 1067 0.811425 746 0.38 850 0.51 939 0.64 1017 0.76 1088 0.891500 773 0.42 875 0.57 963 0.70 1040 0.84 1110 0.96CFMAVAILABLE EXTERNAL STATIC PRESSURE (in. wg)1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHPMedium Static Option High Static Option900 1016 0.51 1080 0.57 1139 0.64 1195 0.71 1249 0.77975 1034 0.57 1098 0.64 1157 0.72 1213 0.79 1266 0.861050 1053 0.63 1116 0.71 1176 0.79 1231 0.87 1284 0.951125 1073 0.70 1135 0.79 1194 0.87 1250 0.96 1302 1.041200 1093 0.77 1155 0.87 1213 0.96 1268 1.05 1321 1.141275 1113 0.85 1174 0.95 1232 1.05 1287 1.15 1339 1.251350 1133 0.92 1194 1.03 1252 1.14 1307 1.25 1358 1.351425 1154 1.01 1215 1.12 1272 1.24 1326 1.35 1378 1.461500 1175 1.09 1235 1.22 1292 1.34 1346 1.46 1397 1.58NOTE: For more information, see General Fan Performance Notes.Boldface indicates field supplied drive is required.1. Recommend using field supplied fan pulley (part no. KR11AG006) and belt (part no. KR30AE039).