33Table 12 — Damper Minimum Position Settings and Readings on Checkout MenuTable 13 — Dry Bulb Operation No DCV (CO 2 Sensor) — 1 Speed Fan*With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on second stage of mechanical cooling Y2-O after the delay if the call forY1-I and Y2-I have not been satisfied.Table 14 — Dry Bulb Operation With DCV (CO 2 Sensor) — 1 Speed Fan*With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on second stage of mechanical cooling Y2-O after the delay if the call forY1-I and Y2-I have not been satisfied.DEMAND CONTROLLEDVENTILATION(CO2 SENSOR)FAN SPEED SETPOINTS CHECKOUTNO1 MIN POS VMAX–HSN/A N/A2 MIN POS H VMAX–HSMIN POS L VMAX–LSYES1 VENT MIN VMAX–HSVENT MAX VMAX–HS2VENT MIN H VMAX–HSVENT MAX H VMAX–LSVENT MIN L N/AVENT MAX L N/ADEMANDCONTROLLEDVENTILATION (DCV)OUTSIDE AIRGOOD TOECONOMIZEY1-I Y2-I FANSPEED Y1-O Y2-O OCCUPIED UNOCCUPIEDNONE NOOFF OFF HIGH 0v/Off 0v/Off MIN POS ClosedON OFF HIGH 24v/On 0v/Off MIN POS ClosedON ON HIGH 24v/On 24v/On MIN POS ClosedNONE YESOFF OFF HIGH 0v/Off 0v/Off MIN POS ClosedON OFF HIGH 0v/Off 0v/Off MIN POS to FullOpen Closed to Full-OpenON ON HIGH 24v/On 0v/Off* MIN POS to FullOpen Closed to Full-OpenDEMANDCONTROLLEDVENTILATION (DCV)OUTSIDE AIRGOOD TOECONOMIZEY1-I Y2-I FANSPEED Y1-O Y2-O OCCUPIED UNOCCUPIEDBelow CO2 SetNoOFF OFF HIGH 0v/Off 0v/Off VENTMIN ClosedON OFF HIGH 24v/On 0v/Off VENTMIN ClosedON ON HIGH 24v/On 24v/On VENTMIN ClosedYesOFF OFF HIGH 0v/Off 0v/Off VENTMIN ClosedON OFF HIGH 0v/Off 0v/Off VENTMIN toFull-Open Closed to Full-OpenON ON HIGH 24v/On 0v/Off VENTMIN toFull-Open Closed to Full-OpenAbove CO 2 SetNoOFF OFF HIGH 0v/Off 0v/Off VENTMIN toVENTMAX ClosedON OFF HIGH 24v/On 0v/Off VENTMIN toVENTMAX ClosedON ON HIGH 24v/On 24v/On VENTMIN toVENTMAX ClosedYesOFF OFF HIGH 0v/Off 0v/Off VENTMIN toVENTMAX ClosedON OFF HIGH 0v/Off 0v/Off VENTMIN toFull-Open Closed to Full-OpenON ON HIGH 24v/On 0v/Off* VENTMIN toFull-Open Closed to Full-Open