35Table 18 — Dry Bulb Operation With DCV (CO 2 Sensor) — 2 Speed Fan*With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on second stage of mechanical cooling Y2-O after the delay if the call for Y1-I andY2-I have not been satisfied.Table 19 — Enthalpy Operation No DCV (CO2 Sensor) — 2 Speed Fan*With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on second stage of mechanical cooling Y2-O after the delay if the call for Y1-I andY2-I have not been satisfied.Table 20 — Enthalpy Operation With DCV (CO 2 Sensor) — 2 Speed Fan*With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on second stage of mechanical cooling Y2-O after the delay if the call for Y1-I andY2-I have not been satisfied.DEMANDCONTROLLEDVENTILATION (DCV)OUTSIDE AIRGOOD TOECONOMIZEY1-I Y2-I FANSPEED Y1-O Y2-O OCCUPIED UNOCCUPIEDBelow CO2 SetNoOFF OFF LOW 0v/Off 0v/Off VENTMIN ClosedON OFF LOW 24v/On 0v/Off VENTMIN ClosedON ON HIGH 24v/On 24v/On VENTMIN ClosedYesOFF OFF LOW 0v/Off 0v/Off VENTMIN ClosedON OFF LOW 0v/Off 0v/Off VENTMIN toFull-Open Closed to Full-OpenON ON HIGH 24v/On 0v/Off VENTMIN toFull-Open Closed to Full-OpenAbove CO 2 SetNoOFF OFF LOW 0v/Off 0v/Off VENTMIN toVENTMAX ClosedON OFF LOW 24v/On 0v/Off VENTMIN toVENTMAX ClosedON ON HIGH 24v/On 24v/On VENTMIN toVENTMAX ClosedYesOFF OFF LOW 0v/Off 0v/Off VENTMIN toVENTMAX ClosedON OFF LOW 0v/Off 0v/Off VENTMIN toFull-Open Closed to Full-OpenON ON HIGH 24v/On 0v/Off* VENTMIN toFull-Open Closed to Full-OpenDEMANDCONTROLLEDVENTILATION (DCV)OUTSIDE AIRGOOD TOECONOMIZEY1-I Y2-I FANSPEED Y1-O Y2-O OCCUPIED UNOCCUPIEDNO CO2 SENSORNOOFF OFF LOW 0v/Off 0v/Off MIN POS ClosedON OFF LOW 24v/On 0v/Off MIN POS ClosedON ON HIGH 24v/On 24v/On MIN POS ClosedYESOFF OFF LOW 0v/Off 0v/Off MIN POS ClosedON OFF LOW 0v/Off 0v/Off MIN POS to FullOpen Closed to Full-OpenON ON HIGH 24v/On 0v/Off* MIN POS to FullOpen Closed to Full-OpenDEMANDCONTROLLEDVENTILATION (DCV)OUTSIDE AIRGOOD TOECONOMIZEY1-I Y2-I FANSPEED Y1-O Y2-O OCCUPIED UNOCCUPIEDBelow CO2 SetNoOFF OFF LOW 0v/Off 0v/Off VENTMIN ClosedON OFF LOW 24v/On 0v/Off VENTMIN ClosedON ON HIGH 24v/On 24v/On VENTMIN ClosedYesOFF OFF LOW 0v/Off 0v/Off VENTMIN ClosedON OFF LOW 0v/Off 0v/Off VENTMIN toFull-Open Closed to Full-OpenON ON HIGH 24v/On 0v/Off VENTMIN toFull-Open Closed to Full-OpenAbove CO 2 SetNoOFF OFF LOW 0v/Off 0v/Off VENTMIN toVENTMAX ClosedON OFF LOW 24v/On 0v/Off VENTMIN toVENTMAX ClosedON ON HIGH 24v/On 24v/On VENTMIN toVENTMAX ClosedYesOFF OFF LOW 0v/Off 0v/Off VENTMIN toVENTMAX ClosedON OFF LOW 0v/Off 0v/Off VENTMIN toFull-Open Closed to Full-OpenON ON HIGH 24v/On 0v/Off* VENTMIN toFull-Open Closed to Full-Open