19Commissioning, inter lock functionCommunication C95In order to have communication between two EP102 panels, C95 should be set to the appropriatevalues..On the first panel C95 is set to 1 and on the second C95 is set to 2.The first panel starts sending values to the second panel, which answers by returning values. WhenC95=0 communication is off. As soon as another value than 0 is set communication starts.If the communication does not work an error message is shown.E14=Error in communication, second panel does not answer.The error message is shown as long as the communication is broken and will continue to show untilboth panels are correctly set. Error message will also be shown if one of the EP 102 panels is withoutpower.Heat Lock, C64=1Only one door can be opened at a time, C64=1 is set on both EP 102 panels. Opening is possible onlywhen the other door is closed. Both doors can shut independently of each other.Eg:: To work automatically set C62=3. By sending a signal to the panel the first doors opens, closesand opens then the other door.If the stop circuit is broken for more than 5 sec. the door is regarded as disabled and the other doorcan be opened independently. (Breaking the interlock during the summer).Description: The first door is opened. When in the fully open position the stop button with lock ispressed. The second door can then be independently operated, although the first door is open.To reset the heat lock function make sure that the second door is in closed position before releasingthe stop button.Blocking of open C64=2Can only be opened when the other door is open. The other door is than set to C64=3.To set both EP 102 to C64=2 is not allowed since when both are closed it is not possible to open.Eg: (C62=3 is set.) A barrier is set to C64=2 and a gate is set to C62=3. When sending a signal toprog. input 1 on the barrier the gate will open and when it is open it will send a signal back to thebarrier which will open. If automatic closing is activated the barrier closes first and when it is closed itcloses the gate.Blocking of close C64=3Can only close if the other door is closed. To set both EP 102 to C64=3 is not allowed since when bothdoors are open it is not possible to close.Ex: (C62=3 is set). A gate is set to C64=3 and a barrier is set to C64=2. When sending a signal toProg. input 1 the gate will open and when it is open it will send a signal to the barrier which opens. Ifautomatic closing is activated the barrier closes first and then the gate.