25Error messagesE01=Motor protector motor 1 tripped out.E02=Motor protector motor 2 tripped out.Possible reasons:Motor running sluggishly or seized, disengage to test.Blown fusePhase error.Break in cable to motor, or in motor winding.Is correct limit for motor protector set? (C44,C45).E03=Max. running time exceeded.Is correct running time set?Mechanical error, drive disengaged.E04=Safety test (autotest). Requires voltage to be cut off for resetting.Is safety circuit properly connected?Can any extraneous voltage get into the circuit?E05=Illegal running. Requires voltage to be cut off for resettingControl panel registers that motor is on whenit should be disengaged.Someone has overridden the contactors.E06=No current motor 1.E07=No current motor 2.Phase error.Blown fuse.Break in cable to electric motor.E08=Voltage loss, brief dip, 24V.E09=Program watchdog tripped out.Powerful interference, e.g. thunderstorm.E10=Clock monitoring error.Error in control panel program clock.E11=Repeated restarting of automatic controls.Short circuit in safety circuit.E12=Memory error. Change program circuit.E13=Incorrect program circuit programming. Change circuit.E14=Communication fault, external unit not answering.Reset by pressing any button at the displayCorrect polarity on the communications cable?Break in communications cable?Correct set up on EP 102?E15=Voltage loss, brief dip, 230V.