ESIE09-08 Troubleshooting by Indication on the Remote ControllerTroubleshooting 1493.15 “E4” Outdoor Unit: Actuation of Low Pressure SensorRemote ControlDisplayE4ApplicableModelsER*Q 011~016*Method ofMalfunctionDetectionAbnormality is detected by the pressure value with the low pressure sensor.MalfunctionDecisionConditionsError is generated when the low pressure is dropped under specific pressure.Operating pressure: 0.07MPaSupposedCauses Abnormal drop of low pressure (Lower than 0.07MPa) Defect of low pressure sensor Defect of outdoor unit PC board (A1P) Stop valve is not opened.