ESIE09-08 Special ControlFunction 553.4 Stopping OperationOperation of the actuator when the system is down, is cleared up.3.4.1 When System is in Stop ModeOUTDOORINDOORActuator OperationCompressor OFFOutdoor unit fan OFFFour way valve Keep former condition.Main electronic expansion valve (EV1) 0 plsSubcooling electronic expansion valve (EV3) 0 plsHot gas bypass valve (SVP) OFFEnding conditions Request for space heating OR hot waterproductionActuator OperationCompressor OFF4-way valve Keep former condition.Pump OFFElectronic expansion valve K1E - R-410A 0 plsElectronic expansion valve K2E - R-134a 0 plsEnding conditions Request for space heating OR hot waterproduction