Test Operation ESIE09-0876 Test Operation1.3.1 Important information regarding the refrigerant usedThis product contains fluorinated greenhouse gases covered by the Kyoto Protocol. Do not ventgases into the atmosphere.Refrigerant type: R-410AGWP (1) value: 1975(1) GWP = global warming potentialPlease fill in with indelible ink, c the factory refrigerant charge of the product, d the additional refrigerant amount charged in the field and c + d the total refrigerant chargeon the refrigerant charge label supplied with the product.The filled out label must be adhered in the proximity of the product charging port (e.g. onto theinside of the service cover).1.3.2 Procedures for adding refrigerantHow to connect the tank?Caution Automatic refrigerant charging is NOT POSSIBLE. Make sure to turn ON the power 6 hours before starting the operation. This is necessary towarm the crankcase by the electric heater.total refrigerant chargeoutdoor unitContains fluorinated greenhouse gasescovered by the Kyoto Protocolfactory refrigerant charge of the product:see unit name plateadditional refrigerant amount chargedin the fieldrefrigerant cylinder andmanifold for chargingContains fluorinated greenhouse gases covered by the Kyoto Protocol1 Liquid line stop valve2 Gas line stop valve3 To indoor unit4 Valve A5 R-410A tank6 Measuring instrument7 Pipe fixing plate3561 243561 274