SiK401004_AINSTALLATION 804. ELECTRIC WIRING WORK4.1 Wiring Principle4.1.1 General Perform wiring of the power supply in conformance with the regulations of the localelectric company. For the control wires connecting indoor units, and between indoor and outdoor units,use of double-core shield wires is recommended to prevent noise trouble. Be sure to set the earth leakage breaker and the switches to the power supply sectionof the indoor unit. Supply power to each outdoor unit and provide an earth leakage breaker or handswitch for each outdoor unit. Store wiring system for control and refrigerant piping system in the same line. Arrange the cables so that the electric wires do not come to contact withhigh-temperature part of the refrigerant pipe; otherwise coating melts and an accidentmay be happened. Do not turn on power of the indoor unit until vacuuming of the refrigerant pipe will becompleted. Installation should be conducted by Local Wiring Regulation. The rated voltage and exclusive power supply must be adopted for the airconditioners. The power cable should be reliable and fixed, in order to avoid the wiring terminal besuffered from force. And do not drag the power cable forcibly. The wire diameter of power cable should be large enough. If power cable andconnection wire be damaged; it should be replaced by the exclusive cable. All electric installation must be done by specialist according to local law, regulation andthis manual. It should be reliably grounded, and it should be connected to the special earth device,the installation work should be operated by the professional. The creep age protect switch and breaker must be installed. Breaker should have the thermal dropout and magnetic dropout function, in order toavoid the short circuit and overload. The on site connection should refer to the circuit diagram, which is stuck on the unitbody. The unit should be reliably grounded, if it is improperly grounded that may causeelectric shock or fire. Air conditioner is the “I” class electric appliance, thus please do conduct reliablegrounding measure. The yellow-green two-color wiring of air conditioner is grounding wire and cannot beused for other purposes. It cannot be cut off and be fixed by screw, otherwise it wouldcause electric shock. The user must offer the reliable grounding terminal. Please don’t connect thegrounding wire to the following places: Water pipe Gas pipe Blowing pipe Other places that specialist consider them unreliable