SiK401004_AINSTALLATION 864.3 Specification of Power Supply Wire and Air Switch4.3.1 Outdoor UnitCapacity ofbreakerMinimum SectionalArea of Earth WireMinimum SectionalArea of PowerSupply WireModel Power Supply(V, Ph, Hz)(A) (mm 2 ) (mm 2 )RY24PEV1KR24PEV1K 220-240, 1, 50 25 4.0 4.0RY30PEV1KRY30PEV1K 220-240, 1, 50 25 4.0 4.0RY36PEY1KR36PEY1K 380-415, 3, 50 20 4.0 4.0RY42PEY1KR42PEY1K 380-415, 3, 50 25 4.0 4.0RY48PEY1KR48PEY1K 380-415, 3, 50 25 4.0 4.04.3.2 Indoor Unit Duct TypeCapacity ofbreakerMinimum SectionalArea of Earth WireMinimum SectionalArea of PowerSupply WireModel Power Supply(V, Ph, Hz)(A) (mm 2 ) (mm 2 )FD(Y)M24PEV1K 220-240, 1, 50 6 1.0 1.0FD(Y)M30PEV1K 220-240, 1, 50 6 1.0 1.0FD(Y)M36PEV1K 220-240, 1, 50 10 1.5 1.5FD(Y)42PEV1K 220-240, 1, 50 10 1.5 1.5FD(Y)48PEV1K 220-240, 1, 50 10 1.5 1.5