Service Mode SiME281501E17 Remote Controller3. Service Mode3.1 BRC1C61/BRC1D613.1.1 Display Service Data1. Enter the field setting mode.Press the INSPECTION/TEST button for 4 seconds or more.2. Enter the service mode.After having entered the field setting mode, press the INSPECTION/TEST button for 4 seconds or more.3. Select the mode No.Set the desired mode No. with the up/down temperature setting button.4. Select the unit No.Select the indoor unit No. set with the time mode START/STOP button.5. Select the desired error history No. or thermistor data No. with “ ” or “ ” button.6. Each data displays (Refer to the table below display)7. Return to the normal operation mode.Press the INSPECTION/TEST button once.Mode No. Function Content and Operation Method Example of Remote Controller Display40 Error History You can change the history with theprogramming time up-down button.41 Thermistor DataDisplay Select the display thermistor withthe programming time up-downbuttonDisplay thermistor00: Room temperature thermistor inremote controller01: Suction air thermistor02: Heat exchanger thermistor2 763 45 31Unit No.SecondCode No.FirstCode No.Mode No.FieldSettingModeUNIT N O.past errorcodeCODE SETTINGError history : Newest: Oldest13 ∼∗ "00" displayed for 4 and subsequent.UNIT No.Thermistor typeTemperatureSETTING